How many receptacle outlets are permitted on a 20amp,
120volt circuit in a commercial building? ...... ANSWER
....... 13✓✓
For show window lighting, a load of not less than 660VA
linear meter or ————- VA linear foot shall be included for
show window measured horizontally along its base. ......
ANSWER ....... 200✓✓
, Page 2 of 101
Open conductors belonging to separate circuits must be
separated by? ...... ANSWER ....... Per NEC 225.14,
separated by 4in. ✓✓
What is the feeder or service calculated load for a , waste
disposal (940VA) dishwasher (1250VA) trash compactor
(1100VA) and a water heater (4500VA)? ...... ANSWER .......
940+ 1250+ 1100+ 4500= 7790/.75= 5843VA✓✓
A load demand factor of 75% is permitted for ________ or
more appliances fasten in place such as waste disposal,
dishwasher, thrash compactor, water heater, ETC ......
ANSWER ....... Four 220. 53✓✓
What is the feeder or service calculated or service
calculated load for a waste disposal (940VA) Dishwasher
(1250VA) and a Warner heater (4500 VA) ...... ANSWER
....... 940+ 1250 + 4500= 6690VA✓✓
Open conductors shall be _________ on glass or porcelain
knobs, racks, brackets, or stain insulators ...... ANSWER
....... Supported✓✓
, Page 3 of 101
Open conductors installed outside shall be separated from
open conductors of other circuits or systems by not less
than ______ ...... ANSWER ....... 4 inches✓✓
Overhead feeder conductors shall have a minimum ____feet
vertical clearance over residential property and driveways,
as well as those commercial areas not subject to truck
traffic, where the voltage is limited to 300V to-ground. ......
ANSWER ....... 12feet✓✓
The minimum clearance for overhead feeder conductors not
exceeding 600V that pass over commercial areas subject to
truck traffic is: ...... ANSWER ....... 18 feet✓✓
Conductors are considered outside a building when they are
buried under not less than _________ ...... ANSWER ....... 2
inches of concrete✓✓
Service conductors installed as unjacketed multi-conductor
cables shall have a minimum clearance of_________ from
windows that are designated to be opened , doors , porches
, Page 4 of 101
, stairs , fire escapes or similar locations. ...... ANSWER
....... 3 feet✓✓
Service drop installed over roofs shall have a vertical
clearance of __________ above the roof surface, unless a
lesser distance is permitted by an exception ...... ANSWER
....... 8 feet✓✓
When the service disconnecting means is a power operated
switch or circuit breaker , it shall be able to be opened by
hand in the event of a __________ ...... ANSWER .......
Power supply failure✓✓
The vertical clearance from ground level over residential
driveways for overhead service conductors not subject to
truck traffic and less than 300 volts to ground shall be
___________ ...... ANSWER ....... 12 feet✓✓
Where it is impracticable to located the service head above
the point of attachment , the service head location shall be
permitted not farther than _______ from the point of
attachment ...... ANSWER ....... 24 inches✓✓