WITH CORRECT ANSWERS!!
100% - ANSWERThe control mechanisms on positive pressure supply system shall
provide what percentage of the peak calculated demand?
Veterinary facilities - ANSWERApplication of the NFPA 99 shall apply to all EXCEPT
which of the following?
6030 or 6040 - ANSWERWhich of the following does NFPA 99 consider an
acceptable qualification for an individual performing maintenance on a Category 1
medical gas systems?
25' - ANSWERChoose the correct distance for the location at capital letter D
riser valve in an open position - ANSWERIdentify A
Filtration shall be sized a minimum of 50% of peak demand. - ANSWERInlet filtration
of the medical-surgical vacuum central supply systems shall contain EXCEPT which
of the following essentials?
At the source equipment - ANSWERIf the system (source gas) is used to verify the
piping purity, it shall also be tested____.
After the blow down of the distribution piping - ANSWERWhen is the initial pressure
test conducted by the installer?
Service valve - ANSWERIdentify number 6
In-line valve - ANSWERIDENTIFY #6
chemical symbol - ANSWERAll piping for station outlets & inlets shall be identified as
to the name or _____ for the specific medical support gas or vacuum provided.
ASSE 6040 - ANSWERThe maintenance of a Category 1 medical gas system must
be preformed by individuals trained & certified by health care facility or a person
certified in which of the following Code/ Standard?
when brazing procedures have been qualified by a competent agency. -
ANSWERUnder which of the following conditions is it permissible to preform work as
an ASSE 6010 installer?
Category 1 space - ANSWERIdentify Area C