● RECORDS OF ALL INSPECTIONS AND MX SHALL BE
MAINTAINED ON PREMISES FOR A MIN. OF __________
YEARS.. Answer: 3
● THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO
COMPLY WITH REQUIREMENTS.. Answer: IMPAIRMENT
COORDINATOR
● REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE
THAN ________ FLOOR(S) ARE CONSIDERED PLANNED
REMOVAL FROM SERVICE.. Answer: 1
● SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S)
ARE CONSIDERED UNPLANNED OUT OF SERVICE
CONDITIONS.. Answer: 1
● NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED
SYSTEM IS RETURNED TO SERVICE WITHIN ______ HOURS..
Answer: 8
,● FOR UNPLANNED REMOVAL FROM SERVICE, THE COF
HOLDER SHALL IMMEDIATELY REPORT CONDITION TO THE
___________ AND THE FIRE DEPT.. Answer: OWNER OF THE
BUILDING
● IF A MINOR DEFECT IS OBSERVED, IT SHALL BE
CORRECTED WITHIN _________ DAYS OR IT WILL BE
CONSIDERED AN IMPAIRMENT.. Answer: 30
● WHAT DOES "OOS" STAND FOR?. Answer: OUT OF SERVICE
● OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________
AT FIRE DEPT. CONNECTIONS, SYS. CONTROL VALVES, AND
FIRE COMMAND CENTER. Answer: TAGS
● A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN
CONTROL VALVE AND ANY SECTIONAL VALVES.. Answer:
MASTER FIRE SUPPRESSION PIPING CONTRACTOR
● __________ SHALL BE POSTED ON THE TAG INDICATING
BOTH STATIC AND FLOW PRESSURES BEFORE AND AFTER..
Answer: DRAIN TEST RESULTS
,● GREEN TAGS INDICATE THAT __________.. Answer: NO
IMPAIRMENT WAS FOUND
● GREEN TAGS WILL BE PLACED ON THE ____________..
Answer: MAIN CONTROL VALVE
● SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL
HAVE A ____________ TAG PLACED ON THE MAIN CONTROL
VALVE.. Answer: RED
● A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON
CONNECTIONS TO INDICATE THE SYSTEM IS FULLY OUT OF
SERVICE.. Answer: WHITE
● A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON
CONNECTIONS TO INDICATE THE SYSTEM IS PARTIALLY OUT
OF SERVICE.. Answer: BLUE
● THE IMPAIRMENT COORDINATOR WILL NOTIFY THE
___________ CARRIER, CENTRAL STATION AND OCCUPANTS..
Answer: INSURANCE
● PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________
SHALL ENSURE THAT NECESSARY TESTS AND INSPECTIONS
ARE CONDUCTED.. Answer: IMPAIRMENT COORDINATOR
, ● GLYCERIN NOT GREATER THAN _________ PERCENT OR
GLYCOL NOT GREATHER THAN ________ PERCENT SHALL BE
USED TO PROTECT FROM FREEZING.. Answer: 50, 40
● THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL
BE POSTED NEAR THE ____________.. Answer: MAIN CONTROL
VALVE
● __________ SHALL BE READILY AVAILABLE TO ANY
REPRESENTATIVE OF THE FIRE DEPT. THESE ARE TO BE
MAINTAINED ON SITE FOR 3 YEARS.. Answer: RECORDS
● FAILURE TO MAKE INSPECTIONS MAY RESULT IN
__________ OF THE COF AND COURT PROCEEDINGS.. Answer:
REVOCATION
● THE COF HOLDER MAY INSPECT, TEST, AND PERFORM
ROUTINE MX IF THEY HOLD THE FOLLOWING CERTS:. Answer:
REFRIGERATION OPERATING ENGINEER, HIGH PRESSURE
OPERATING ENGINEER, AND NYS HIGH PRESSURE
OPERATING ENGINEER.
● A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL
FIRE STANDPIPE AND SPRINKLER SYSTEMS.. Answer: MASTER
FIRE SUPPRESSION PIPING CONTRACTOR (MFSPC)