A confined space is:
a) not meant for continuous employee occupancy
b) limited in entry and exit
c) large enough so that an employee can enter and perform work
d) all of the above - CORRECT ANSWERS d) all of the above
Title 8 CCR, section 5157(b)
All of the following are not exempt from UST regulations EXCEPT:
a) heating oil tanks
b) waste oil tanks
c) motor vehicle fuel tanks
d) aviation fuel tanks - CORRECT ANSWERS a) heating oil tanks
Title 23 CCR, section 2621(a)(2)
The following is an approved quantitative method of non-visual monitoring for existing UST systems:
a) ground water monitoring
b) vadose zone monitoring
c) statistical inventory reconciliation
d) interstitial sensor - CORRECT ANSWERS c) statistical inventory reconciliation
Title 23 CCR, section 2643(b)(3)
In order to meet the requirements for "Fail Safe", the monitoring system must shut down the turbine
pump during which of the following:
a) power outage
b) monitoring system fails
c) monitoring system disconnect
d) all of the above - CORRECT ANSWERS d) all of the above
Title 23 CCR, section 2611
If a hazardous substance is stored in a basement, which of the following conditions will exempt the
container from UST regulation?
a) the container capacity is greater than 1320 gallons
b) the tank is emptied every 30 days
, c) the container is corrosion-protected
d) the amount stored is 55 gallons or less - CORRECT ANSWERS d) the amount stored is 55
gallons or less
Title 23 CCR, section 2621(a)(13)
"(13) Drums located in basements and which contain 55 gallons or less of a hazardous substance."
When an ATG is utilized for single-walled tank leak detection, it shall generate a post-test hard copy
report of the following information EXCEPT:
a) liquid volume
b) fuel depth
c) outside air temperature
d) time and date of test - CORRECT ANSWERS (c) outside air temperature
Title 23 CCR, section 2643(b)(1)
The following are "new underground storage tanks" EXCEPT:
a) tanks installed prior to January 1, 1984
b) tanks installed after January 1, 1987
c) farm tanks that store motor vehicle fuel for the purpose of resale
b) tanks installed for emergency generators at hospitals - CORRECT ANSWERS a) tanks
installed prior to January 1, 1984
Title 23 CCR, section 2611
Effective July 1, 1991, what information must be located on the exterior surface of a new UST?
a) engineering standard, capacity, year manufactured, location of manufacturer
b) engineering standard, diameter, intended storage material, year manufactured
c) diameter, capacity, year manufactured, manufacturer
d) all of the above - CORRECT ANSWERS c) diameter, capacity, year manufactured,
manufacturer
Title 23 CCR, section 2631(b)
A monitoring program must:
a) be approved by the local agency
b) be specified in the UST operating permit
c) include the frequency of performing the monitoring
d) all of the above - CORRECT ANSWERS d) all of the above
Title 23 CCR, section 2632(b) and section 2632(d)(1)(a)
If two successive statistical inventory reconciliation reports are inconclusive, a tank integrity test must
be accomplished within ____ days of receipt.