Systems Layout Detailed Exam
Study Questions with 100%
Correct Answers | Already Graded
A+
1. The area of the floor or fire area and exit locations, as well as the occupancy
classification - ANSWER What determines the number and locations of
hose connections?
2. Local building codes - ANSWER What determines the types of standpipe
systems, classes of systems, and locations of hose connections?
3. Number of hose connections flowing, the quantity of water flowed, the
required residual pressure, and the vertical and horizontal distance of those
hose connections from the water supplies. - ANSWER What is the
standpipe piping size dependent on?
4. 350psi - ANSWER The maximum pressure at any point in the standpipe
system at any time shall not exceed?
5. An early suppression fast-response (ESFR) system is protecting in-rack
storage of a Group A plastic commodity, stacked to 35 feet (10.67 meters).
Under which condition can antifreeze be used? - ANSWER If the solution
and the sprinkler head are specifically listed for use with antifreeze
,6. What is the minimum size of the heat circulating pipes required for a
100,000 gallon elevated steel tank in an area where the minimum 1-day
mean temperature is -30 F - ANSWER 3-inch NFPA 22 16.1.7.1
7. In a general stack area of a library, the ceiling has a slope of 3-in-12 and is
22 feet high at the lowest point. What is the hydraulic area of operation for a
dry system? - ANSWER 2535 square feet per NFPA 13 section 19.2.3.2.4
and 19.2.3.2.5
8. In an exterior canopy constructed of combustible material above a 400
square foot area used for pedestrian foot traffic, where are sprinklers
required? - ANSWER In the concealed space, and below the canopy ceiling
9. A 750 gpm pump is located 25 feet from the test header. What size should
the test header be? - ANSWER 6-inch
10.What two pieces of information are required on drawings submitted to the
AHJ when a tank is the water supply? (Chose two.) - ANSWER
Arrangement of all pipes and location of all valves
11.When installing a new backflow prevention device in an existing system,
which three pieces of information are required to be submitted to the AHJ?
(Chose Three) - ANSWER 1. Hydraulic calculations to prove design
performance for hazard classification. 2. location of backflow prevention
device in the existing system. 3. manufactures data sheet of new backflow
prevention device
12.Which detail is one purpose of architectural drawings? - ANSWER
communicate scope of work
, 13.For fire pump and jockey pump installations, where should the pump
controller's pressure sensing lines be connected? - ANSWER individual
from each other
14.A sprinkler is 3 feet away from a gas powered unit heater in a 2,000 square
foot garage. What should be the temperature rating of the sprinkler? -
ANSWER High temp 286 degrees
15.In a new apartment building where the highest floor for use is 45 feet above
the lowest level for fire department access, which type of standpipe is
required? - ANSWER wet automatic
16.What is the minimum fire-resistance rating for a fire partition that separates
dwelling units in the same building that in constructed of Type VB (5B)
construction and a sprinkler system in accordance with International
Building Code (IBC) section 903.3.1.1 ? - ANSWER 1/2 hour per IBC
708.3
17.A contractor submits hydraulic calculations for a wet system with black steel
pipe. The calculations are based on a C value of 120. The AHJ rejects the
calculations because the local building code requires a value of 100 to be
used for wet and dry systems. The contract requires the contractor to follow
NFPA 13 and local building codes. What should the contractor do? -
ANSWER Revise the calculation to comply with the local code
requirements
18.A 45000 square foot building with 40 feet of elevation to the roof has
required exit stairways and a Class I manual dry standpipe system. A roof
manifold is located 3 feet above the roof. The total amount of friction loss in
the pipe is 8 psi. What is the required flow and pressure at the fire
department connection (FDC) located 3 feet above finished grade? -
ANSWER 750 gpm and 126 psi (2,480 liters per minute and 8.6 bar)