MED GAS PART 3 EXAM QUESTIONS
WITH CORRECT DETAILED ANSWERS
_____________ is considered by the NFPA 99 to acceptable qualification for an
individual performing maintenance on a category 1 medical gas system. - Answer-ASSE
6030 or 6040
Inlet filtration of the medical surgical vacuum central supply systems shall contain filters
efficient to 99.7%, filters shall be at least duplex, on patient side of the vacuum pump
but does not ___________. - Answer-Shall be sized a minimum of 50% peak calculated
demand.
It is not permissible to pipe and utilize medical gas as oxygen for ________. - Answer-
General utility such as moisture removal from instruments
Manifolds for gas cylinders and manifolds for cryogenic liquid containers both have -
Answer-Primary and secondary headers shall be located in the same room
Under what condition should the instrument air reserve headed cylinders shall be
permitted to be stored with the instrument air compressor? - Answer-The only motor
driven machinery in the room is for the instrument air equipment
What treatment shall be performed BEFORE brazing cut ends of a tube used for piping
medical gas? - Answer-Cut ends shall be rolled smooth or deburred
Manifolds for cryogenic liquid containers, if located outdoors, shall be installed so that
minimum separation of _______ feet exist between portable cryogenic and room exits. -
Answer-3
What is not a requirement for bulk oxygen system installed to supply compressed gas? -
Answer-Maximum storage must be 25,000 sq ft
What is the minimum required footage between medical surgical vacuum exhaust and
the air intake of another building? - Answer-25 ft
Qualified individuals installing CMT shall do so in accordance to which of the following?
- Answer-Manufacturers instructions
Carbon dioxide cylinders shall NOT reach temperatures greater than how many
degrees Fahrenheit? - Answer-125
What is not a requirement of a computer system used as a substitute for master alarms
in a medical gas or vacuum alarm system? - Answer-Operating programs used to
WITH CORRECT DETAILED ANSWERS
_____________ is considered by the NFPA 99 to acceptable qualification for an
individual performing maintenance on a category 1 medical gas system. - Answer-ASSE
6030 or 6040
Inlet filtration of the medical surgical vacuum central supply systems shall contain filters
efficient to 99.7%, filters shall be at least duplex, on patient side of the vacuum pump
but does not ___________. - Answer-Shall be sized a minimum of 50% peak calculated
demand.
It is not permissible to pipe and utilize medical gas as oxygen for ________. - Answer-
General utility such as moisture removal from instruments
Manifolds for gas cylinders and manifolds for cryogenic liquid containers both have -
Answer-Primary and secondary headers shall be located in the same room
Under what condition should the instrument air reserve headed cylinders shall be
permitted to be stored with the instrument air compressor? - Answer-The only motor
driven machinery in the room is for the instrument air equipment
What treatment shall be performed BEFORE brazing cut ends of a tube used for piping
medical gas? - Answer-Cut ends shall be rolled smooth or deburred
Manifolds for cryogenic liquid containers, if located outdoors, shall be installed so that
minimum separation of _______ feet exist between portable cryogenic and room exits. -
Answer-3
What is not a requirement for bulk oxygen system installed to supply compressed gas? -
Answer-Maximum storage must be 25,000 sq ft
What is the minimum required footage between medical surgical vacuum exhaust and
the air intake of another building? - Answer-25 ft
Qualified individuals installing CMT shall do so in accordance to which of the following?
- Answer-Manufacturers instructions
Carbon dioxide cylinders shall NOT reach temperatures greater than how many
degrees Fahrenheit? - Answer-125
What is not a requirement of a computer system used as a substitute for master alarms
in a medical gas or vacuum alarm system? - Answer-Operating programs used to