TFM02
Distilled Water - ANSWERS-water mist extinguishers can only
use________
False - ANSWERS-For safety, portable extinguishers should NOT be
installed in a location accessible to the hazard.
date printed on the nameplate - ANSWERS-all nonrechargable
extinguishers come w/ maximum useful life cycles of no more
than______
unventilated locations - ANSWERS-carbon dioxide extinguishers can be
dangerous in ______________
True - ANSWERS-Extinguishers should be CO2 or halogenated agent
types when computer equipment is in the location of fire.
A, B, C - ANSWERS-what type of fires can Halotron fight?
END OF
PAGE
1
, TEXAS EXT TYPE B LATEST
TFM02
CleanguardFE 36 - ANSWERS-suitable replacement for Halon 1211
because it is less toxic and has 0 ozone depletion potential.
30 - ANSWERS-the pressure in a hydrostatic test of a cylinder shall
maintained for a minimum of ____ sec.
dry chemical and dry powder - ANSWERS-on certain _ (cartridge
operated)
dry chemical and halogenated extinguishers - ANSWERS-require 6 &
12 yr hydrostatic testing
water, afff, fffp, CO2 extinguishers - ANSWERS-require 5 yr
maintenance and hydrostatic testing
Class A rating - ANSWERS-wood
class b rating - ANSWERS-2" depth heptane fires in square pans
END OF
PAGE
2
, TEXAS EXT TYPE B LATEST
TFM02
a fire extinguisher is rated 4-A: 20-B:C - ANSWERS-it is twice as much
as a 2-A, 20x's as much as 1:B, suitable for C fires
Condemn - ANSWERS-if cylinder has welding, broken threads, nicks or
corrosion
pressure gauges used on test equipment - ANSWERS-calibrated
semiannually
master gauges - ANSWERS-calibrated annually
drying equipment - ANSWERS-shall not exceed 150F
DOT 3E cartridges or TC 3EM cartridges - ANSWERS-exempt from
periodic hydrostatic testing
30 seconds - ANSWERS-hydrostatic test of cylinder shall be maintained
for
END OF
PAGE
3