With a peak ceiling, heat and smoke detectors shall be
located within _____ of the peak, measured horizontally -
Answer-36''
smoke detectors shall not be located near - Answer-Air
supply diffusers
When beams project more than _____ inches below the
ceiling and are more than 8' on center, each bay formed
by the beams shall be treated as a separate area for heat
detectors - Answer-18''
When manual fire alarm boxes are used, the distance
between boxes will not be in excess of - Answer-200'
,2|Page
A water flow device should be field adjusted so that an
alarm is initiated in no more than _____ seconds -
Answer-90 seconds
smoke detectors shall not be located directly in the air
stream of - Answer-supply registers
Detectors shall not be installed until after - Answer-Final
clean up of all trades
a heat detector integrally mounted on a smoke detector
shall be listed and approved for not less than - Answer-50'
Detectors for common return systems should be installed
up to ______ in front or behind openings - Answer-12''
A line-type obsucration smoke detector, where the light
beam is projected across the area to be protected -
Answer-projected beam smoke detector
Where Public Mode audible appliances are installed they
shall be ____________ above average ambient sound
level - Answer-15dba
, 3|Page
Where audible appliances are installed in mechanical
equipment rooms, the average ambient sound level is -
Answer-85dba
An average ambient sound level greater than ______ shall
require the use of a visible notification appliance - Answer-
105dba
All fire detection devices shall be listed or approved for the
purpose for which they are intended - Answer-True
A detector should not be recessed in any way unless they
have been tested for such a mounting - Answer-True
How far from the doorway shall a Manual fire alarm station
be mounted - Answer-5'
Vane type flow switch have no longer than _____ to initiate
alarm - Answer-90 sec
smoke detectors must be tested every - Answer-1 year