QUESTIONS AND SOLUTIONS SCORED A+
✔✔Main isles of storage occupancies shall be a minimum of ______feet wide - ✔✔8
✔✔Flammable Storage Cabinets; Class I, II, and III A liquids shall not exceed
______gallons - ✔✔120
✔✔Not more than ______cabinets in a single fire area - ✔✔3
✔✔Containers; Drums cannot exceed ________gallons - ✔✔119
✔✔Containers; Portable tanks cannot exceed ________gallons - ✔✔660
✔✔Containers; Intermediate bulk containers cannot exceed_______gallons - ✔✔793
✔✔Tanks; Fixed tanks that exceed _______gallons - ✔✔60
✔✔Tanks; Portable tanks that exceed _______gallons - ✔✔660
✔✔Tanks; Intermediate bulk containers that exceed _______gallons - ✔✔793
✔✔Where flammable and combustable liquid storage tanks are within a diked area, the
containers shall be outside the diked are and at least _______ feet away from the
centerline of the wall of the diked area - ✔✔3
✔✔What area shall be a space within a building where quantities of liquids that do not
exceed the maximum quantities are allowed to be stored? - ✔✔A control area
✔✔The Maximum Allowable Quantities per Control Area (MAQ) Flammable Liquids; IA
= _______gallons, IB and IC = _____gallons, IA, IB, and IC combined =
_______gallons - ✔✔30, 120, 120
✔✔The Maximum Allowable Quantities per Control Area (MAQ) Combustable Liquids; II
= ______gallons, III A =_______gallons, III B = _______gallons - ✔✔120, 330, 13200
✔✔NFPA 33 - ✔✔Spray Booths
✔✔Spray booths shall have a fire resistive rating of ______hour - ✔✔1
✔✔Spray rooms shall be separated by a minimum of ______feet or by constructive
assemblies that have a fire resistive rating of _______hour - ✔✔3, 1
, ✔✔Panels for light fixtures shall be separated to prevent temperatures from reaching
and exceeding _______degrees F - ✔✔200
✔✔NFPA 51 - ✔✔Welding and Cutting Operations
✔✔Oxygen cylinders shall be separated from combustables by a minimum of
______feet or by having a barrier ______feet high having a fire resistive rating of at
least _____hour - ✔✔20, 5, 1/2
✔✔Barrier shall interrupt all lines of sight located within ______feet of each other -
✔✔20
✔✔Where combustable materials such as paper clippings, wood shavings, or textile
fibers are on the floor, the floor shall be swept clean for a radius of ______feet - ✔✔35
✔✔Openings or cracks in walls, floors, or ducts within _______feet shall be sealed -
✔✔35
✔✔A fire watch shall be required by the Permit Authorizing Individual when hot work is
performed in a location where fire might develop or.......... - ✔✔(1) Combustables are
closer than 35 feet
(2) Combustables are more than 35 feet but are easily ignited by sparks
(3) Walls or cracks are not sealed if within 35 feet
✔✔Cardinal principle is to expose _______number of people to the _______amount of
ammunition for the _______amount of time - ✔✔minimum, minimum, minimum
✔✔What does a barricade do? - ✔✔Limit the effectiveness of low angle high velocity
fragments
✔✔Above Ground Magazine - ✔✔Building used for the storage of explosives
✔✔Earth Covered Magazine - ✔✔a minimum of 2 feet of earth cover will be maintained
✔✔Open flame shall not be permitted inside or within ______feet of magazine - ✔✔50
✔✔Are shall be kept clear of brush, dried grass, and similar combustables for a
distance of at least ______feet - ✔✔25
✔✔Storage of ______lbs or less of explosive materials shall be fire resistant and theft
resistant - ✔✔50
✔✔AE may not be stored with _______substances or articles - ✔✔dissimilar