SI Certs Fireproofing Practice Test 1-3 | Questions and Answers | 2025/2026
What is the minimum allowable TFIFRM 80% of specified thickness
thickness determination?
How many TFIFRM thickness determinations are required 24
for a W-shape column?
How many TFIFRM thickness readings are required for a 24
pipe column?
Suppose you are performing TFIFRM thickness testing 60 mils
on a truss, and required thickness is 50 mils. What is
the maximum thickness determination you can record
on the report?
Where do you find the requirements for applying TFIFRM? Manufacturer instructions
How long must substrate temperatures be maintained 72 hours
after applying TFIFRM?
, For SFRM application, substrate temperatures must be 40 degrees F, 24 hours
maintained at ___ for ___ after application.
If primer is used on a column beneath SFRM, the column 16 inches
web depth cannot exceed:
When metal lath is used for SFRM application, it must 1.7Ib/cubic yard
weigh at least:
High rise buildings that are 410 feet tall must have an 430 psf
SFRM bond strength of at least:
How many SFRM thickness measurements are required 4
for a metal deck that uses a flat plate?
When would a drill bit be used for SFRM inspection? When thickness testing high density SFRM
A wide flange column is required to have 2 inches of 1-3/4 inch
SFRM thickness. What is the lowest allowable individual
thickness measurement?
A tube steel column is required to have 1 inch of SFRM 1 inch
thickness. What is the lowest allowable individual
thickness measurement?
Which type of failure describes a separation between Adhesive
SFRM and substrate?
When testing SFRM thickness on a joist, 7 thickness 12 inch
measurements are taken at each end of a ___ length.
When testing a W-shaped column for SFRM thickness, the Yes, all acceptance criteria is met
specified thickness is 1-7/16 inch. 2 of the measurements
are 1-3/16 inch and 1-1/4 inch while the rest are above 1-
7/16 inch. Is this acceptable?
How many SFRM thickness tests are required underneath 7
metal decking that is 6,500 sf?
What is the SFRM bond strength if the test cap area 260 psf
is 0.0576 square feet and the force at SFRM failure is
15 pounds?
When drying SFRM for density testing, what is the 119 degrees F
maximum allowable temperature?
SFRM thickness gauges must be capable of reading to 1/16-inch.
the nearest:
What is the minimum allowable TFIFRM 80% of specified thickness
thickness determination?
How many TFIFRM thickness determinations are required 24
for a W-shape column?
How many TFIFRM thickness readings are required for a 24
pipe column?
Suppose you are performing TFIFRM thickness testing 60 mils
on a truss, and required thickness is 50 mils. What is
the maximum thickness determination you can record
on the report?
Where do you find the requirements for applying TFIFRM? Manufacturer instructions
How long must substrate temperatures be maintained 72 hours
after applying TFIFRM?
, For SFRM application, substrate temperatures must be 40 degrees F, 24 hours
maintained at ___ for ___ after application.
If primer is used on a column beneath SFRM, the column 16 inches
web depth cannot exceed:
When metal lath is used for SFRM application, it must 1.7Ib/cubic yard
weigh at least:
High rise buildings that are 410 feet tall must have an 430 psf
SFRM bond strength of at least:
How many SFRM thickness measurements are required 4
for a metal deck that uses a flat plate?
When would a drill bit be used for SFRM inspection? When thickness testing high density SFRM
A wide flange column is required to have 2 inches of 1-3/4 inch
SFRM thickness. What is the lowest allowable individual
thickness measurement?
A tube steel column is required to have 1 inch of SFRM 1 inch
thickness. What is the lowest allowable individual
thickness measurement?
Which type of failure describes a separation between Adhesive
SFRM and substrate?
When testing SFRM thickness on a joist, 7 thickness 12 inch
measurements are taken at each end of a ___ length.
When testing a W-shaped column for SFRM thickness, the Yes, all acceptance criteria is met
specified thickness is 1-7/16 inch. 2 of the measurements
are 1-3/16 inch and 1-1/4 inch while the rest are above 1-
7/16 inch. Is this acceptable?
How many SFRM thickness tests are required underneath 7
metal decking that is 6,500 sf?
What is the SFRM bond strength if the test cap area 260 psf
is 0.0576 square feet and the force at SFRM failure is
15 pounds?
When drying SFRM for density testing, what is the 119 degrees F
maximum allowable temperature?
SFRM thickness gauges must be capable of reading to 1/16-inch.
the nearest: