KENTUCKY BOILER EXAM LATEST 2026 ACTUAL EXAM WITH
COMPLETE QUESTIONS AND CORRECT DETAILED ANSWERS (100%
VERIFIED ANSWERS) |ALREADY GRADED A+| ||PROFESSOR
VERIFIED|| ||BRANDNEW!!!||
If the owner or user of a boiler or P.O. required to be inspected
refuses to allow inspection or refuses to pay the fees____ -
ANSWER-The certificate shall be suspended by the
commissioner until the owner complied with requirements in
krs236 or 815 kar chapter 15
How often shall pressure vessels exceeding 200psi MAWP be
inspected ? - ANSWER-Every 5 years
How often shall hot water storage tanks, sterilizers, and
autoclaves be inspected? - ANSWER-every 4 years
How often shall pressure vessels for human occupancy and
hyperbaric chambers be inspected? - ANSWER-Every 2 years
How often shall jacketed kettle be inspected? - ANSWER-Every 2
years
,2|Page
How often shall deaerators be inspected? - ANSWER-Every 10
years
T/F : all pressure vessels shall be re-inspected at the time of
repair, alteration, or relocation - ANSWER-True
T/F: inspections made by boiler inspectors shall be conducted
during normal business hours between 8 and 5 m-f - ANSWER-
True
Who prepares the boiler if inspection is requested? - ANSWER-
Owner or user
Within how many days of notice by the inspector shall inspection
be conducted? - ANSWER-7 days
For code boiler, how is the MAWP determined? - ANSWER-Shall
be determined in accordance with the original code of
construction
, 3|Page
For no code boilers, how is the MAWP determined? - ANSWER-
Shall be calculated in accordance with Section 1 of the ASME
Boiler and Pressure Vessel Code
For non code welded heating boilers, what is the MAWP -
ANSWER-Shall not exceed 15 psi
For other than steam service, how shall the MAWP be determined
- ANSWER-Shall be calculated in accordance with section IV of
the ASME Boiler and Pressure Vessel Code as established by
KRS 236.040
The MAWP of no code boiler composed principally of cast iron
shall not exceed ________ for steam service and _____ for hot
water service - ANSWER-15psi and 30 psi
If an accident renders a boiler inoperative, who shall notify the
department and submit a detailed report of the accident -
ANSWER-Owner, user, or insurer