up to three AFFF or FFFP fire extinguishers of at least...
2 1/2 gallon capacity shall be permitted to be used to fulfill extra
hazard requirements
Wheeled fire extinguishers of 125 lbs aent capacity or larger are
installed or positioned for obstacle, gravity, / 3 - dimensional, or
pressure fire hazards...
the actual travel distance to hazard shall not exceed 100ft unless
otherwise specified
Fire extinguishers or extinguishers or extinguishing agents shall be
located not more than ...
75ft of travel distance from the class D hazard
Class K fire extinguishers shall be provided for hazards where there
is the potential for fires involving ....
combustible cooking media
,(Class K) Max travel distance to extinguisher shall not exceed...
30 ft
All solid fuel cooking appliance w/ fire boxes of 5ft volume or less
shall have atleast
Listed 2-A rated water-type extinguisher or a 1.6 gallon wet chemical
fire extinguisher
(Ch. 7 - I, M, Re) Responsibility
Owner/operator/agent is responsible for inspection maintenance and
recharging
(Ch. 7 - I, M, Re) - persons training to be certified must be while
inspecting
under direct supervision of a certified person
(Ch. 7 - I, M, Re) - persons inspecting ...
don't need licenses however...
(Ch. 7 - I, M, Re) - Replacement while servicing -
when a fire extinguisher is serviced an equal extinguisher must be put
in its place
, (Ch. 7 - I, M, Re) - Tags or labels intended for recording inspections
maintenance or recharging
have to be affixed so they arent in the way of showing the
inspection, maintenance, class, etc.
(Ch. 7 - I, M, Re) - Tags and Labels showing use/class/or
Manufacterers labels have to go ...
on the front of the extinguisher
when fire extinguishers are initially placed into service they need to be
...
manually inspected
When conditions are harsh/hazardous to the ext. cylinder they need to
be
manually inspected daily/weekly
Inspection Procedure
1. Located in designated place
2. no obstruction to access or visibility
3. pressure gauge reading or indicator in operable range
4. fulless determined by lifting or hefting or weighing
5. condition of wheels, tires, carriage, hose, and nozzle
for wheeled extinguishers
6. indicator for nonrechargeable extinguishers using push to
test pressure indicators