A 32,000 square foot office building d.32,000 VA
has 120 20-ampere, 120-volt duplex
receptacle outlets. What is the Note: 220.14(K) - use largest of either 1 VA per
branch circuit receptacle load? square foot or 180 VA per outlet.
Select one:
a.9,600 VA 180 VA × 120 = 21,600 VA32,000 ft2 × 1
b.21,600 VA
c.28,000 VA VA = 32,000 VA
d.32,000 VA
An AC charger with a single-phase a.Level 1
120-volt connection and 14-16
amperes of continuous current
output is classified as a ? charger.
Select one:
a.Level 1
b.Level 2
c.low-voltage
d.SAE standard
,According to Article 625, EVSE is c.the premises wiring system
equipment that has the specific
purpose of transferring energy from
? to the electric vehicle.
Select one:
a.a DC power source
b.a generator
c.the premises wiring system
d.the utility
According to the ADA guidelines, b.4%
what percentage of general parking
spaces should be accessible?
The acronym RFID stands for ? . a.radio frequency identification
Select one:
a.radio frequency identification
b.recognized ferrite input detection
c.reduced fuel in direction
ADA guidelines are useful when d.all of the above
planning an EVSE installation
because ? .
Select one:
a.there are no federal standards for
EVSE accessibility
b.they establish clear space around
equipment that allows for wheelchair
approach and access
c.they establish equipment
characteristics that increase
accessibility
d.all of the above
, Additional EVSEs are to be added to c.6
an existing 120/208-volt, 3-phase, 4-
wire, 600-ampere service with 220 220 A + (172 A × 1.25) = 435 A
amperes of non-continuous load and
172 amperes of continuous load. The 600 A - 435 A = 165 A
EVSEs each draw 32 amperes. How
many new EVSEs can be added to 165 A × 0.8 = 132 A left (due to EVSEs being
the service? (Note: Use 1.732 for the continuous loads)
square root of 3.)
Select one: (32 × 1.732) = 55.43
a.2
b.3 132 A / 55.43 = 2.38 or 2 per phase
c.6
d.9 Total = 6 EVSEs
Adequate site lighting increases the a.True
safety of an EVSE location.
Select one:
a.True
b.False
The CHAdeMO V1.0 Standard has a.62.5 kW / 500 VDC / 125 A
charging power up to ? at ? , up to ? .
Select one:
a.62.5 kW / 500 VDC / 125 A
b.350 kW / 480 VDC / 80 A
c.400 kW / 1,000 VDC / 400 A
d.1 MW / 2,200 VDC / 800 A