1. Audible appliances shall be mounted at least ______ inches
above the floor if ceiling height permits - correct answer -90
2. Audible appliances shall be mounted at least _____ inches
below the ceiling. - correct answer -6
3. The flash rate of a visible device cannot exceed ____ flashes
per second and must be at least ____ flashes per second. -
correct answer -2,1
4. Wall mounted visible appliances shall be mounted between
____ inches and ____ inches above the floor. - correct answer
-80, 96
5. The maximum distance between visible appliances in a corridor
can be no more than: - correct answer -100 ft
, Page | 2
6. There must be a visible appliance at least ____ feet from the
end of a corridor. - correct answer -15
7. In a sleeping room the visible appliance can be no further than
____ feet from the pillow. - correct answer -16
8. Two or more visible notification appliances are required to be
synchronized except: - correct answer -Household applications
9. The minimum a sound level of a notification appliance in a
sleeping room is: - correct answer -75 dbA
10. Sound level measurement requirements are defined per a
______ specification. - correct answer -ANSI
11. A coded alarm signal shall consist of a minimum of ____
rounds of ____ impulses. - correct answer -3, 3