COMPLETE QUESTIONS WITH CORRECT
DETAILED ANSWERS || 100% GUARANTEED PASS
LATEST VERSION
Save
Terms in this set (60)
Dead-end corridors are limited to ___ 30 feet
feet in new and existing health care
occupancies.
For new health care occupancies, 200 ft
the travel distance between any
point in a room and an exit may not
exceed _____.
The travel distance between any 50 feet
point in a health care sleeping room
and an exit access door in that room
may not exceed ____.
A common path of travel in a new 100 feet
health care occupancy may not
exceed ___.
,In a new health care occupancy what B. one-third of the building or area diagonal
distance must separate the two exit measurement
access doors?
A. One-third of the building or area's
longest wall
B. One-third of the building or area
diagonal measurement
C. One-fourth of the building or
area's longest wall
D. One-fourth of the building or area
diagonal measurement
Which of the following statements D. Supplemental requirements, such as a two-way
about areas of refuge is true? communication system apply to areas of refuge.
A. An area of refuge must have
smoke-resisting partitions.
B. An area of refuge must have
sprinkler protection.
C. The Code requires areas of refuge
in all buildings.
D. Supplemental requirements, such
as a two-way communication system
apply to areas of refuge.
Intervening rooms in a patient D. Are not limited in number
sleeping room with not more than
eight beds:
A. Are limited to one per room
B. Are limited to two per room
C. Are limited to three per room
D. Are not limited in number
, When a second exit access is B. One exit access door must be to the corridor
required in a suite:
A. One exit access door must be to
an exit stair
B. One exit access door must be to
the corridor
C. Both exit access doors must be to
the corridor
D. Both exit access doors may be to
adjoining suites
Where two exits in a new health care False
occupancy are remotely located,
their exit discharge points need not
be remotely located. T/F
Accessible means of egress is D. An area of refuge, a horizontal exit, or a public
defined as a means of egress that way
provides an accessible route to:
A. An area of refuge or a public way
B. An area of refuge or a horizontal
exit
C. An area of refuge or a ramp
D. An area of refuge, a horizontal
exit, or a public way
What chapter of the Life Safety Code C. Chapter 7
establishes minimum requirements
for the means of egress?
A. Chapter 4
B. Chapter 6
C. Chapter 7
D. Chapter 8