When testing a water level supervisory switch serving a pressure tank a
signal shall indicate if the water level _____________from the required level
(NFPA 72, Table 14.4.3.2 17 (j) (4)
Ans: rises or falls over 3 inches
If combination audible/visible appliances are installed the location of the
Assignment Expert
installed appliance shall be determined by the requirements of _______.
(Nfpa 72 18.4.8.1)
Guru01 - Stuvia
Ans: the visible appliance
What is the maximum number of 12 gauge THHN wires that can be
installed in 1" EMT?
2026
(Nec Annex C tables)
©
Ans: 26
Two resistors are connected in parallel. R1 = 300 Ohms, R2 = 300 Ohms.
What is their equivalent resistance?
Ans: 150 ohms
A Room is 200' long and 150' wide and the 8' high ceiling is smooth and
flat. A spot type heat detector has been selected that is listed for a 50'
maximum spacing between detectors. According to NFPA 72 how many
detectors will be needed to protect this room?
x =
Ans: 12
, 2 for specific request mail
According to NFPA 72 the minimum number of restorable fixed
temperature spot type heat detectors that must be tested during each
annual test is?
(NFPA 72 14.4.4.5.1)
Ans: Two detectors or more on each initiating device circuit
According to NFPA 72 how many spot type heat detectors are required for
a space that is 80' long and 55 floor wide with a smooth 10' ceiling? the
detector is listed for a maximum space between detectors of 30'
Ans: 6
Assignment Expert
What color code requirement for a spot type heat detector rated at 200 ゚ F
Guru01 - Stuvia
Ans: White (NFPA 72, Table 17.6.2.1)
Unless otherwise recommended by the manufacturers published
instructions single and multiple stations smoke alarms installed in one
2026
and 2 family dwellings shall be replaced every
Ans: 10 years from the day-of manufacture. (NFPA 72, 14.4.7.1)
©
Fire alarm cables are permitted to be strapped to conduit to support the
cable
Ans: False (NEC 760.143)
Where non power limited wiring is installed exposed it must be
mechanically protected within_____of the finished floor
Ans: 7' ft
Fire-Warning equipment to be installed in residential occupancies shall
produce the audible emergency evacuation signal described in
Ans: ANSI S3.41
According to NFPA 72, visible notification appliance for non-sleeping
areas must be mounted between ___ and ___ inches above the finished
, 3 for specific request mail
floor
Ans: 80 & 96
If system impairment occurs, the owner must be notified ___ within ___
Ans: in writing & within 24 hours
A 20 X 20' ft room with a 20'ft high ceiling requires at a minimum a ___
ceiling mounted strobe
Ans: 30 candela
According to NFPA 72, a 40 x 40'ft room or area with a 10'ft ceiling is best
Assignment Expert
covered by a ___ cd visible notification appliance, centered on one wall.
Ans: 60
Guru01 - Stuvia
Conductors returning to the fire alarm control panel (FACP) from the last
field device on the circuit might indicate a _____ circuit
Ans: Class A
2026
Secondary power supplies for an emergency voice/alarm communication
fire alarm system shall be capable of operating for minimum of ___ of
©
standby followed by ___ of alarm.
Ans: 24 hrs & 15 mins
The fire alarm system primary power branch circuit disconnecting means
must be ___ in color.
Ans: Red
The secondary power supply for protected premises shall automatically
provide power within ___ seconds when primary power fails.
Ans: 10 seconds
Under which of the following conditions shall spot-type smoke detectors
NOT be installed?
Ans: When the temperature is over 100*F
Nicet level 1 Study Guide Questions | Accurate &
Verified Answers to Pass Actual Exam
When testing a water level supervisory switch serving a pressure tank a
signal shall indicate if the water level _____________from the required level
(NFPA 72, Table 14.4.3.2 17 (j) (4)
Ans: rises or falls over 3 inches
If combination audible/visible appliances are installed the location of the
Assignment Expert
installed appliance shall be determined by the requirements of _______.
(Nfpa 72 18.4.8.1)
Guru01 - Stuvia
Ans: the visible appliance
What is the maximum number of 12 gauge THHN wires that can be
installed in 1" EMT?
2026
(Nec Annex C tables)
©
Ans: 26
Two resistors are connected in parallel. R1 = 300 Ohms, R2 = 300 Ohms.
What is their equivalent resistance?
Ans: 150 ohms
A Room is 200' long and 150' wide and the 8' high ceiling is smooth and
flat. A spot type heat detector has been selected that is listed for a 50'
maximum spacing between detectors. According to NFPA 72 how many
detectors will be needed to protect this room?
x =
Ans: 12
, 2 for specific request mail
According to NFPA 72 the minimum number of restorable fixed
temperature spot type heat detectors that must be tested during each
annual test is?
(NFPA 72 14.4.4.5.1)
Ans: Two detectors or more on each initiating device circuit
According to NFPA 72 how many spot type heat detectors are required for
a space that is 80' long and 55 floor wide with a smooth 10' ceiling? the
detector is listed for a maximum space between detectors of 30'
Ans: 6
Assignment Expert
What color code requirement for a spot type heat detector rated at 200 ゚ F
Guru01 - Stuvia
Ans: White (NFPA 72, Table 17.6.2.1)
Unless otherwise recommended by the manufacturers published
instructions single and multiple stations smoke alarms installed in one
2026
and 2 family dwellings shall be replaced every
Ans: 10 years from the day-of manufacture. (NFPA 72, 14.4.7.1)
©
Fire alarm cables are permitted to be strapped to conduit to support the
cable
Ans: False (NEC 760.143)
Where non power limited wiring is installed exposed it must be
mechanically protected within_____of the finished floor
Ans: 7' ft
Fire-Warning equipment to be installed in residential occupancies shall
produce the audible emergency evacuation signal described in
Ans: ANSI S3.41
According to NFPA 72, visible notification appliance for non-sleeping
areas must be mounted between ___ and ___ inches above the finished
, 3 for specific request mail
floor
Ans: 80 & 96
If system impairment occurs, the owner must be notified ___ within ___
Ans: in writing & within 24 hours
A 20 X 20' ft room with a 20'ft high ceiling requires at a minimum a ___
ceiling mounted strobe
Ans: 30 candela
According to NFPA 72, a 40 x 40'ft room or area with a 10'ft ceiling is best
Assignment Expert
covered by a ___ cd visible notification appliance, centered on one wall.
Ans: 60
Guru01 - Stuvia
Conductors returning to the fire alarm control panel (FACP) from the last
field device on the circuit might indicate a _____ circuit
Ans: Class A
2026
Secondary power supplies for an emergency voice/alarm communication
fire alarm system shall be capable of operating for minimum of ___ of
©
standby followed by ___ of alarm.
Ans: 24 hrs & 15 mins
The fire alarm system primary power branch circuit disconnecting means
must be ___ in color.
Ans: Red
The secondary power supply for protected premises shall automatically
provide power within ___ seconds when primary power fails.
Ans: 10 seconds
Under which of the following conditions shall spot-type smoke detectors
NOT be installed?
Ans: When the temperature is over 100*F