with verified detailed answers || || ||
The smallest size locking and grounding type receptacle that may be used to provide shore
|| || || || || || || || || || || || || || ||
power for boats is _____. - ✔✔30A
|| || || || || ||
A commercial kitchen with more than six pieces of kitchen equipment is subject to a demand
|| || || || || || || || || || || || || || || ||
factor of _____. - ✔✔65%
|| || || ||
What is the load for 40 non-dwelling unit receptacles? (Assume that the load is not
|| || || || || || || || || || || || || || ||
continuous.) - ✔✔7,200VA || ||
Refer to the figure provided. What is the total load of a feeder serving four 230V motors rated
|| || || || || || || || || || || || || || || || || ||
5hp, 15hp, 20hp, and 40hp? - ✔✔241.2A
|| || || || || ||
The demand lighting load for a 20,000 ft2 motel with no dining room or ballroom is _____. -
|| || || || || || || || || || || || || || || || || ||
✔✔17,600VA
A roadside vegetable stand has a continuous load of 2,000VA and a noncontinuous load of
|| || || || || || || || || || || || || || ||
500VA. The total load is _____. - ✔✔3,000VA
|| || || || || || ||
What is the feeder ampacity for a three-phase, 120/208V subpanel with a connected load of
|| || || || || || || || || || || || || || ||
84,563VA? - ✔✔235A || ||
When performing load calculations for farm buildings, the load that must be included in the
|| || || || || || || || || || || || || || ||
calculation at 100% demand must be at least _____. - ✔✔60A || || || || || || || || || ||