For terminations using wire binding screws, conductors not larger than
___________________ are not allowed -CORRECTANSWER 10 AWG (110.14(A))
The high leg of a delta system must be ________________________ -
CORRECTANSWER Orange (110.15)
Minimum DEPTH of a clear working space is -CORRECTANSWER 3' (110.26(A))
Minimum width of working space is ___________ or the width of the equipment,
whichever is greater. Doors must open at least ____________ -CORRECTANSWER
30in, 90 Degrees (110.26(A)(2))
Minimum Height of working space is _________________ , or the height of equipment,
whichever is greater. -CORRECTANSWER 6'1/2" (110.26(A)(3))
Equipment over ____________________ or more than _____ ft. wide require
_________ entrances to the working space. -CORRECTANSWER 1200A, 6', 2
(110.26(C)(2))
, Dedicated equipment space extends from floor to __________ above the equipment or
structural ceiling -CORRECTANSWER 6' (110.26(E))
What section covers enclosure types, such as NEMA 3R, which provides protection
from incidental contact, rain, and snow and sleet? -CORRECTANSWER (110.28)
Grounded conductors must be ___________________ -CORRECTANSWER white,
gray, or three continuous white or gray stripes along insulation other than green (200.6)
GFCI Protection Requirements are in which section? What are they? -
CORRECTANSWER (210.8)
Required circuits for dwelling units Include? -CORRECTANSWER (2) 20A Small
Appliance Circuits
(1) 20A Laundry Receptacle
(1) 20A Bathroom Branch Circuit
(1) 20A Garage Circuit
All 125-volt, 15- and 20-ampere receptacles installed in the following locations shall
have GFCI protection: -CORRECTANSWER Dwellings:
Bathrooms
Garages and work rooms of similar use