Questions and Answers | Correct
Answers | Graded A+
‣ What are the 3 funtions of an Oil Burner nozzle? -✓✓Atomize, Meter,
Patter.
‣ What are the 2 voltage circuits of a primary control? -✓✓Line & Low.
‣ What is the function of a fuse? -✓✓Protect circuit.
‣ What is the High Limit cut out? -✓✓Max safe Temp or Pressure
setting.
‣ What is the High Limit cut in? -✓✓Cut out minus Differential.
‣ What is the "Max" Lockout time for a burner with a 3 GPH Flow Rate?
-✓✓45 Seconds.
‣ What is the minimum stack temperature which will allow a stack
switch to work? -✓✓400 degrees F
‣ When do you apply a permit to store oil? -✓✓10 gallons.
, ‣ What is the "Main" function of an oil burner Primary Control? -
✓✓Prove Flame.
‣ Stack Relay must be reset after lockout? True? or False? -✓✓True.
‣ What is the Required minimum height required for fill and vent pipes?
-✓✓3 Feet.
‣ What is the smallest vent pipe used for residential. -✓✓1 inch 1/4
‣ What size is the oil line for a residential burner? -✓✓3/8
‣ Largest oil capacity for residential without a license? -✓✓10,000
Gallons
‣ At what height ceiling would a second thermal switch be required? -
✓✓12'
‣ A typical residential oil burner is also s/u to run Kerosene True? Or
False? -✓✓False
‣ Permit to install an oil burner is issued by the? -✓✓State Fire Marshall