Q: Where is the union located for a gas appliance?
Answer:
A union fitting shall be provided for appliance connected by rigid metallic pipe. Such unions
shall be accessible and located within 6 feet of the appliance.
Q: Where is gas piping permitted?
Answer:
Gas piping may be installed in public corridors in residential buildings that do not have floors
below grade or in multi use buildings that have a residential occupancy in accordance with the
following, Gas piping shall be permitted to be installed within a public corridor at the lowest
level of the building or the lowest residential level of the building. All gas valves located within
the public corridor shall be accessible for maintenance and inspection. Gas pressure within the
public corridor piping shall not exceed 1/2 psi. The completed piping within the public corridor
is to be tested and proven tight at 10 psig for a minimum of 30 minutes. The public corridor
shall be ventilated in accordance with the New York City Mechanical Code. The pipe shall not be
installed in a return air plenum. Pipes must be welded.
1
,Q: How much must piping for other than dry gas conditions be sloped?
Answer:
Not less the 1/4 inch in 15 feet to prevent traps.
Q: Hanger spacing for 3/4 inch and 1 inch gas pipe
Answer:
8 feet
Q: When is water permitted for testing?
Answer:
Fresh water may be used the test medium where the required test pressure exceeds 100 p.s.i.g.
Q: When do need temporary restraints when testing?
Answer:
Expansion joints shall be provided with temporary restraints, if required, for the additional trust
load under test.
2
, Q: What must each digital gauge used to measure pressure in the magnitude of 3 and higher
read?
Answer:
The gauge shall have a minimum reading of 1/100 of a p.s.i.g.
Q: Where pipe passes through an outside wall, this piping shall not be less than how many
inches outside of the buildings?
Answer:
With conduit going through the wall, pipe shall not be less than 4 inches outside the building
and sleeve shall be at least 1 inch beyond the inner side of the wall. Pipe shall be vented above
grade to the outdoors and shall be installed so as to prevent the entrance of water and insects.
Q: Threaded pipe may be used up to 4 inches at pressure no greater than?
Answer:
1/2 p.s.i.g.
Q: Gas piping going through the foundation wall of a building, shall be protected by?
Answer:
Encasing it in a protective sleeve.