EXAM WITH CORRECT ACTUAL
QUESTIONS AND CORRECTLY WELL
DEFINED ANSWERS LATEST ALREADY
GRADED A+
Which of the following statements about alarm systems that
provide occupant notification in health care occupancies is
true?
A. All new and existing systems must have audible and
visual signals
B. Visible alarm and appliances can be used in critical care
areas
C. Visual signals are recommended but not required for new
systems
D. Visible alarm and appliances only can be used in sleeping
areas - ANSWERS-B. Visible alarm and appliances can be
used in critical care areas
,In new health care occupancies, initiation of the alarm
system is to be by:
A. Manual means and sprinkler system waterflow alarms
B. Manual means and automatic detection
C. Sprinkler system waterflow alarms and extinguishing
system operation
D. Manual means and extinguishing system operation -
ANSWERS-A. Manual means and sprinkler system waterflow
alarms
Which of the following statements about smoke detectors in
new health care occupancies is NOT true?
A. They are required in spaces open to the corridor without
direct visual supervision.
B. They are required in corridors in nursing homes.
C. They are required in suites having non-separated
hazardous areas.
D. They are required in all patient rooms and corridors. -
ANSWERS-D. They are required in all patient rooms and
corridors.
, Portable fire extinguishers:
A. Are required for all health care occupancies
B. Are required for existing health care occupancies
C. Are required only in kitchen areas for new health care
occupancies
D. Are prohibited for all health care occupancies -
ANSWERS-A. Are required for all health care occupancies
Which of the following statements about smoke barriers in
new health care occupancies is true?
1010
A. Fire-rated glazing is not allowed
B. Single doors are allowed in the means of egress corridor
C. Smoke barrier wall rating of at least ½-hour is required
D. Smoke barrier wall rating of at least 1-hour is required -
ANSWERS-D. Smoke barrier wall rating of at least 1-hour is
required
Which building rehabilitation category applies to the
reconfiguration of a space, such as removing a wall between
two rooms?