◉ RECORDS OF ALL INSPECTIONS AND MX SHALL BE
MAINTAINED ON PREMISES FOR A MIN. OF __________ YEARS.
Answer: 3
◉ THE BUILDING OWNER SHALL ASSIGN A(N) ____________
TO COMPLY WITH REQUIREMENTS. Answer: IMPAIRMENT
COORDINATOR
◉ REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE
THAN ________ FLOOR(S) ARE CONSIDERED PLANNED
REMOVAL FROM SERVICE. Answer: 1
◉ SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S)
ARE CONSIDERED UNPLANNED OUT OF SERVICE
CONDITIONS. Answer: 1
◉ NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED
SYSTEM IS RETURNED TO SERVICE WITHIN ______ HOURS.
Answer: 8
,◉ FOR UNPLANNED REMOVAL FROM SERVICE, THE COF
HOLDER SHALL IMMEDIATELY REPORT CONDITION TO THE
___________ AND THE FIRE DEPT. Answer: OWNER OF THE
BUILDING
◉ IF A MINOR DEFECT IS OBSERVED, IT SHALL BE
CORRECTED WITHIN _________ DAYS OR IT WILL BE
CONSIDERED AN IMPAIRMENT. Answer: 30
◉ WHAT DOES "OOS" STAND FOR? Answer: OUT OF SERVICE
◉ OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________
AT FIRE DEPT. CONNECTIONS, SYS. CONTROL VALVES, AND
FIRE COMMAND CENTER. Answer: TAGS
◉ A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN
CONTROL VALVE AND ANY SECTIONAL VALVES. Answer:
MASTER FIRE SUPPRESSION PIPING CONTRACTOR
◉ __________ SHALL BE POSTED ON THE TAG INDICATING
BOTH STATIC AND FLOW PRESSURES BEFORE AND AFTER.
Answer: DRAIN TEST RESULTS
,◉ GREEN TAGS INDICATE THAT __________. Answer: NO
IMPAIRMENT WAS FOUND
◉ GREEN TAGS WILL BE PLACED ON THE ____________.
Answer: MAIN CONTROL VALVE
◉ SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL
HAVE A ____________ TAG PLACED ON THE MAIN CONTROL
VALVE. Answer: RED
◉ A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON
CONNECTIONS TO INDICATE THE SYSTEM IS FULLY OUT OF
SERVICE. Answer: WHITE
◉ A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON
CONNECTIONS TO INDICATE THE SYSTEM IS PARTIALLY OUT
OF SERVICE. Answer: BLUE
◉ THE IMPAIRMENT COORDINATOR WILL NOTIFY THE
___________ CARRIER, CENTRAL STATION AND OCCUPANTS.
Answer: INSURANCE
◉ PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________
SHALL ENSURE THAT NECESSARY TESTS AND INSPECTIONS
ARE CONDUCTED. Answer: IMPAIRMENT COORDINATOR
, ◉ GLYCERIN NOT GREATER THAN _________ PERCENT OR
GLYCOL NOT GREATHER THAN ________ PERCENT SHALL BE
USED TO PROTECT FROM FREEZING. Answer: 50, 40
◉ THE COF NUMBER AND SIGNATURE OF COF HOLDER
SHALL BE POSTED NEAR THE ____________. Answer: MAIN
CONTROL VALVE
◉ __________ SHALL BE READILY AVAILABLE TO ANY
REPRESENTATIVE OF THE FIRE DEPT. THESE ARE TO BE
MAINTAINED ON SITE FOR 3 YEARS. Answer: RECORDS
◉ FAILURE TO MAKE INSPECTIONS MAY RESULT IN
__________ OF THE COF AND COURT PROCEEDINGS. Answer:
REVOCATION
◉ THE COF HOLDER MAY INSPECT, TEST, AND PERFORM
ROUTINE MX IF THEY HOLD THE FOLLOWING CERTS: Answer:
REFRIGERATION OPERATING ENGINEER, HIGH PRESSURE
OPERATING ENGINEER, AND NYS HIGH PRESSURE
OPERATING ENGINEER.
◉ A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL
FIRE STANDPIPE AND SPRINKLER SYSTEMS. Answer: MASTER
FIRE SUPPRESSION PIPING CONTRACTOR (MFSPC)