Exam Newest 2026-2027 With Complete 250
Questions And Correct Detailed Answers| Brand
New Version!
As-Built system installation drawings, hydraulic calculations, original
acceptance test records, and device manufacturer's data sheets shall be
kept for how long? - ANSWER-For the life of the system
Dry System
How often should Dry Pipe Valves have a Full Trip Test? - ANSWER-Every
3 years
Dry System
How often should Quick-Opening Devices be tested? - ANSWER-
Annually
Dry System
1|Page
,How often should Air Pressure Maintenance Devices must be tested? -
ANSWER-Annually
Dry System
When refilling a Dry System, how long should the Air Supply be capable
of restoring to normal air pressure? - ANSWER-30 Minutes
Dry System
Records of Trip Times and Water Transit Delivery Times to the
inspectors test connection, must be kept for a minimum of 1 year after
the following test. - ANSWER--False
-Must be kept for the life of the system
Dry System
After testing a Dry Pipe Valve, a tag shall be attached that has the
following information:
-Company Name
2|Page
,-Testers Name
-Date of Test - ANSWER-True
An Air Compressor with less than _____ cubic feet per minute at 10 PSI,
does NOT require an Air Maintenance Device - ANSWER-5.5
Pre-Action, Dry Systems
When performing a Pressure Test(Hydro) at 40 psi for 2 hours, the
system shall be permitted to lose up to what psi during the duration of
the test? - ANSWER-3psi
When a Trip Test is conducted on a Dry System, how often should the
Interior of a Dry Pipe Valve be Inspected? - ANSWER-Annually
5. Sprinkler Systems
Fast-Response Sprinklers in service for more than how many years, shall
be Replaced or Tested? - ANSWER-20 years
5. Sprinkler Systems
3|Page
, How often should the retesting of Fast-Response Sprinklers occur? -
ANSWER-10 year intervals
13. Common Components and Valves - Main Drain Test
When there is a 10% reduction in full flow pressure when compared to
the original acceptance test or previously performed test, what should
happen? - ANSWER-The cause of the reduction shall be identified and
corrected if necessary.
5. Sprinkler Systems
In an Antifreeze System, how many samples shall be tested? - ANSWER-
-2
-At its most remote portion and where it interfaces with the wet pipe
system.
5. Sprinkler Systems
A building has 630 sprinklers, how many should be tested? - ANSWER--
1%
-7
4|Page