When placing a LOTO on a system, how many locks
should be applied? - ANSWER-As many locks as their are
personnel working on the system.
Dry sprinklers that have been service for _____ yrs shall
be replaced or tested - ANSWER-10
Retesting of dry sprinklers shall occur at _____ yr intervals
- ANSWER-10
,A representative sample of sprinklers for testing shall
consist of a minimum of 4 or ____ % of the number of
sprinklers - ANSWER-1
When a ____ % reduction in full flow pressure is observed
compared to the original acceptance test or previously
performed tests, the cause of the reduction shall be
identified and corrected. - ANSWER-10
When antifreeze systems have a capacity larger than 150
gallons, tests at one additional point shall be conducted for
every ____ gallons shall be made - ANSWER-100
,The lead in to a building supplies a header or manifold
serving 4 systems, how many main drain tests are
required? - ANSWER-1
After testing sprinklers the first time, testing shall be
repeated every ____ yrs - ANSWER-10
Listed CPVC sprinkler systems shall be protected from
freezing with ____ only - ANSWER-Glycerin
I need some fake answers #4 - ANSWER-Diethylene
I need some fake answers #5 - ANSWER-Ethylene
, I need some fake answers #6 - ANSWER-Propylene
Testing a valve supervisory s/w, a signal shall indicate
movement from the control valves normal position during
either the first ____ revolutions or when the stem has
moved 1/5th of the distance from its normal position -
ANSWER-2
Control valve supervisory s/w shall be tested _____ -
ANSWER-Annually
Mechanical waterflow alarm devices shall be tested _____
- ANSWER-Quarterly