Joints shall be brazed within _______ hours after the surfaces are
cleaned for brazing.
a.one
b.eight
c.twenty-four
d.four
b. eight
Final line pressure controls shall be sized to ___ of the peak
calculated demand.
a.50%
b.100%
c.110%
d.Not specified
b. 100%
The scale range of positive pressure analog indicators shall have the
normal reading fall within the _________ percentage of the gauge
scale.
a.1/4
b.1/3
c.1/2
d.2/3
d. 2/3
END OF
PAGE
1
, MED GAS REFRESHER LATEST
EXAM
The accuracy of digital indicators shall be +/- ____ % of the
operating pressure at which they are used.
a.4
b.2
c.5
d.1
c. 5
Vacuum piping for ____________ shall be connected separately
from the medical surgical system directly to the receiver tank
through its own isolation valve and fluid trap located at the receiver.
a.Each WAGD system
b.The standing vacuum test
c.A teaching laboratory
d.A location requiring seismic restraint
c. A teaching laboratory
Which of the following conditions must be met where medical gas
and vacuum systems are installed by non-certified personnel?
a.An installer certified to ASSE 6010 must be present to oversee the
installation
b.An ASSE 6020 inspector is present on the job sit to inspect the
installation
c.The installer must be an employee of an authorized Medical Gas
contractor
END OF
PAGE
2
, MED GAS REFRESHER LATEST
EXAM
d.Installation by anyone other than 6010 certified personnel is NOT
permitted
d. Installation by anyone other than 6010 certified personnel is NOT
permitted
Locations for central supply systems shall have electrical devices
protected from ___________.
a.unauthorized use
b.freezing temperatures
c.physical damage
d.moisture
c. physical damage
Installers of Category 1 medical gas piping systems must be
qualified to ASSE 6010. What is the certification requirement for
installers of a Category 3 system?
a.6010
b.6020
c.6030
d.Category 3 does not require certification
a. 6010
Mock Exam Diagram 1.pdf Refer to Drawing #1. Item #4 is a
______ valve.
a.main line
b.riser
END OF
PAGE
3
, MED GAS REFRESHER LATEST
EXAM
c.service
d.in-line shutoff
c. service
Medical air compressor air intake shall be located outdoors a
minimum distance of ________ above the ground level.
a.10 ft
b.20 ft
c.25 ft
d.There is no height requirement
b. 20 ft
Cylinder and cryogenic liquid container outlet connections shall be
affixed in such a manner as to be intregal to the valve, unremovable
with ordinary tools or so designed as to render the attachment point
________ when removal of the outlet connection is attempted.
a.reusable
b.universal
c.unusable
d.unsuitable
c. unusable
Instrument air systems shall be permitted to interconnect with the
medical air system provided the system has __________.
a.separate source valves for each system
b.been approved by the manufacturer