Medical Gas 6010 Installers ||Verified Exam!!!||Newest
With Complete All 300 Questions And Correct Detailed
Answers|| Newest Exam!!!
Central supply systems for positive pressure gases shall
have one or more relief valves, the valves shall have a
relief setting that is _% above normal working operating
pressure? A) 30 B) 40 C) 50 D) 60 - Answer-C) 50
When vented to the outside, relief valve vent lines shall be
labeled in which way? A) adhesive markers B) any manner
that will distinguish them from the medical gas pipeline C)
stenciling D) stickers - Answer-B) any manner that will
distinguish them from the medical gas pipeline
An auxiliary source connection shall consist of all of the
following except? A) removable plug or cap B) tee C) valve
D) visual pressure indicator - Answer-D) visual pressure
indicator
In central supply systems using gas or liquid cylinders,
each header shall have a _ to prevent debris from entering
the manifold controls? A) check valve B) filter C) monitor
D) relief valve - Answer-B) filter
,2|Page
Manifolds for gas cylinders shall consist of two equal
headers, each with enough cylinders for an average day's
supply, but not fewer than _ connections? A) 5 B) 4 C) 3
D) 2 - Answer-D) 2
Manifolds for gas cylinders shall have a(n) _ signal that
visibly indicates the operating status of the equipment and
shall activate an indicator at all master alarm panels when
or just before changeover from one header to the other
takes place? A) area B) master C) local D) zone - Answer-
C) local
When multiple buildings are served from a single
cryogenic liquid oxygen source, it is required to place the
emergency oxygen supply connection in _ ? A) each
building served B) the building closest to the source C) the
largest building served D) the main building only - Answer-
A) each building served
The minimum clearance around EOSC for a temporary
source of supply is _ ft? A) 2 B) 3 C) 5 D) 6 - Answer-B) 3
,3|Page
A(n) _ emergency reserve system can be substituted for
the EOSC? A) auxiliary B) backup C) in-building D) micro-
bulk - Answer-C) in-building
The quality medical air shall comply with all of the
following standards except? A) be filtered to .01 microns
B) have less than 25 ppm gaseous hydrocarbons C) have
no detectable hydrocarbons D) meet the requirements of
medical air USP - Answer-A) be filtered to .01 microns
An existing system that is not in strict compliance with the
provisions of this code shall be permitted to be continued
in use as long as the _ has determined that such use does
not constitute a distinct hazard to life. A) architect B)
authority having jurisdiction C) engineer D) nursing staff -
Answer-B) authority having jurisdiction
Cylinder and cryogenic liquid container outlet connections
shall be designed as to render the attachment point _
when removal of the outlet connection is attempted. A)
reusable B) unusable C) unsuitable D) universal - Answer-
B) unusable
, 4|Page
Cylinders in use and in storage shall be prevented from
reaching temperatures in excess of _ *F. A) 120 B) 125 C)
130 D) 135 - Answer-B) 125
Nitrous oxide and carbon dioxide using cylinders or
portable containers shall be prevented from reaching
temperatures lower than _ *F A) 130 B)125 C) 20 D) -20 -
Answer-C)20
Which of the following systems shall not be permitted to
be located in an outdoor enclosure? A) bulk cryogenic
liquid cylinders B) manifolds for gas cylinders C) manifolds
for cryogenic liquid containers D) medical air sources -
Answer-D) medical air sources
Indoor locations for oxygen, nitrous oxide, and mixtures of
these gases shall not communicate with any of the
following except _? A) area with open flames B)
designated storage area C) engines D) kitchens - Answer-
B) designated storage area
Locations for central supply systems shall have _ devices
protected from physical damage? A) electrical B) pressure
indicating C) regulating D) relief - Answer-A) electrical