January 1, 2000
July 1, 2005, service techs shall possess or work under someone who has a current certification indicating he or
she has passed the?
ICC UST Service Technician Exam
ICC cert must be renewed every?
24 months
Service techs must possess or be employed by a person who has the appropriate contractor's license unless?
The individual has a tank testing license
Service tech is defined by any individual who?
Tests UST monitoring equipment, trouble shoots UST systems, and/or installs UST monitoring equipment.
,If the manufacturer training no longer exist, the local agency may?
Approve comparable alternate training .
UST includes?
Tank and connected piping
What is considered a UST?
A petroleum underground storage tank.
What UST system meets the requirements for secondary containment?
Doubled wall tanks
According to title 23; the following piping components if installed after July 1, 1987 must have secondary
containment.
Pressured product piping
,What is considered "pipe" on tanks installed after July 1, 2003?
Pressured product piping and below ground vapor recovery.
Under dispenser containment (UDC) was required for all existing UST systems by
December 31, 2003
What system is for exchanging gas vapors in a storage tank and product in a fuel delivery truck
Stage 1 vapor recovery
Which approved method for non-visual monitoring for existing UST systems.
Statistical Inventory Reconciliation (SIR)
ATG must be capable for detecting a release of?
0.2 gallons per hour
, What is no longer an approved method for non-visual monitoring on existing UST systems?
Manual inventory reconciliation.
Automatic line leak detectors installed on underground piping with secondary containment shall be capable
of detecting a leak of ?
3 gallons per hour at 10 psi
How often should ATG be programmed to test the tank?
At least monthly
According to PEI RP 300, a combustible gas can be used to?
Detect vapor leaks in a vapor recovery system.
According to PEI RP 300, a written scope of work for vapor recovery installation should include?
Construction plans