Dwelling Electrical Contractor Licensing
Exam Questions and Answers | 2026
Update | 100% Correct. PDF
1. A residential electrical contractor is wiring a new single-family dwelling. The service
disconnecting means for a 200-amp, single-phase residential service must be located
where?
A) Inside the master bedroom closet for accessibility
B) At the rear of the dwelling farthest from the utility transformer
C) At a readily accessible location either inside or outside the dwelling nearest the point
of entrance of the service conductors
D) Within the attic space above the garage
Correct Answer: C
Rationale: According to the North Carolina Residential Code and NEC 230.70(A)(1), the
service disconnecting means must be installed at a readily accessible location either
outside the building or inside nearest the point of entrance of the service conductors.
This ensures that emergency responders (firefighters) and utility workers can quickly
disconnect power in an emergency without having to search through living spaces.
Closets, attics, and basements with storage are not considered "readily accessible"
unless specifically designed for that purpose.
2. A grounding electrode system for a new home must include a minimum of how many
grounding electrodes unless it is proven that a single electrode has a resistance of 25
ohms or less?
A) One
B) Two
,C) Three
D) Four
Correct Answer: B
Rationale: NEC 250.53(A)(2) requires that if a single grounding electrode (such as a
ground rod) has a resistance greater than 25 ohms to earth, one additional electrode
must be installed. In practice, to avoid testing costs, most residential contractors in NC
install two ground rods spaced at least 6 feet apart by default to comply with this
requirement without needing to perform resistance testing.
3. In a single-family dwelling, what is the maximum height above the floor that a wall
switch controlling a permanently installed light fixture can be placed to be considered
"readily accessible"?
A) 5 feet
B) 6 feet 7 inches
C) 7 feet
D) 8 feet
Correct Answer: B
Rationale: NEC 404.8(A) specifies that switches must be installed so that the center of
the grip of the operating handle, when in the highest position, is not more than 6 feet 7
inches (2.0 m) above the floor or working platform. This is a universal accessibility
requirement to ensure that the average person can reach the switch without requiring a
step stool.
4. When installing Type NM (Romex) cable in a residential attic that is accessible by a
pull-down stair, what protection is required for the cable running perpendicular to the
joists within 6 feet of the scuttle hole?
A) No protection is required if the cable is secured every 4.5 feet
B) Guard strips or running boards
C) The cable must be derated to 50% ampacity
D) Metal conduit only
,Correct Answer: B
Rationale: NEC 320.23(A) (and applicable sections for NM cable) require that where
cables are installed in an attic that is accessible, they must be protected by substantial
guard strips or running boards if they are within 6 feet of the scuttle hole or attic
entrance and run across the top of floor joists. This prevents someone stepping on the
cable and damaging the insulation while walking through the attic.
5. What is the minimum required ampacity for a feeder supplying a 120/240-volt,
single-family dwelling with a calculated load of 150 amps using the Standard Method?
A) 150 amps
B) 160 amps
C) 175 amps
D) 200 amps
Correct Answer: A
Rationale: NEC 310.12 (formerly 310.15(B)(7)) allows for a reduced service or feeder
conductor size for dwelling units. However, the service or feeder rating (the overcurrent
protection device) must be at least the calculated load. If the calculated load is 150A, the
minimum service rating is 150A. The conductor ampacity must be sufficient for the load,
though Table 310.12 permits 4/0 AWG aluminum for 175A or 2/0 AWG copper for 150A
in residential applications.
6. AFCI protection is required for which of the following areas in a new single-family
dwelling in North Carolina?
A) Bathroom receptacle outlets only
B) Kitchen receptacle outlets only
C) All 120-volt, 15 and 20-amp branch circuits supplying outlets in dwelling units
D) Garage door opener receptacles only
Correct Answer: C
Rationale: As of the current adopted NEC version in NC (with amendments), AFCI (Arc-
Fault Circuit Interrupter) protection is required for nearly all 120-volt, 15 and 20-amp
, branch circuits supplying outlets in dwelling units. This includes bedrooms, living rooms,
kitchens, laundry areas, and hallways. While bathrooms and garages often have GFCI
requirements, they also require AFCI unless exempted by local amendments (though the
trend is towards broad coverage).
7. A homeowner requests a ceiling fan installation in a bedroom where the existing
plastic octagon box is currently just a light. What must the electrical contractor do
regarding the box?
A) Install a fan-rated box that is listed for ceiling fan support
B) Leave the plastic box as it is because it supports the light
C) Add a wooden brace in the attic but keep the plastic box
D) Install a metal box with a plaster ring
Correct Answer: A
Rationale: NEC 314.27(D) requires that outlet boxes used for ceiling-suspended (fans)
must be listed and marked as suitable for the support of a ceiling fan. Standard light
fixture boxes are not rated for the dynamic load (vibration and torque) caused by a
rotating fan. Failure to use a fan-rated box is a major safety hazard and a code violation
in North Carolina.
8. What is the minimum burial depth for direct burial Type UF cable in a residential yard
for a circuit rated 120 volts or less with GFCI protection?
A) 6 inches
B) 12 inches
C) 18 inches
D) 24 inches
Correct Answer: B
Rationale: NEC Table 300.5 specifies that direct burial cables (UF) for residential branch
circuits rated 120 volts or less, with GFCI protection, and with overcurrent protection not
exceeding 20 amps, require a minimum cover of 12 inches. If GFCI protection is not
utilized, or the voltage is higher, the depth increases to 24 inches.