Verification of performance of inspection and testing Verify that the installed system meets the operation requirements of the version of
programs shall do which of the following to code when the system was installed, verify the correct operation of the system.
Which of the following shall be done when conducting Annually conduct a discharge test with the charger disconnected while
tests in lead-acid type batteries conducting a load test with full alarm load or an artificial load,
Area of refuge two-way communication systems are Verify Receipt of visual and audible signal at the transmitting and receiving unit,
required to be tested in which of the following three respectively
ways
How often shall secondary power supply be tested? Annually
How often are video image smoke and fire detectors Annually
required to be inspected?
Which two of the following are true regarding acceptable Shall be documented with the testing records, shall be written to clearly establish
test plans? the scope of the testing for the fire alarm or signaling system.
How often shall fire optic cable connections be Annually
inspected?
How many years after the initial installation shall all fixed 20 Years
temperature non restorable line type detectors be
replaced or have 2 per 100 laboratory tested?
How often are digital alarm communicator transmitters Annually
required to be inspected?
How are rate of rise heat detectors tested? Heat gun or something similar