A fire alarm system zone should not exceed _____ feet in 300
any direction
NFPA 72-A.10.18.5(5)
While conducting fire alarm systems work, a splice in a Boxes
notification circuit is required. According to NFPA 70, Enclosures
cable splices shall be made in_____? Fire Alarm Devices
NFPA 70-760.130(B)(1)
, Consider electrical metallic tubing. There shall not be 360
more than the equivalent of ____ degrees total between
pull points, for example conduit bodies and boxes?
NPFA 70-358.26
Power Limited fire alarm circuit conductors shall be 2
separated by at least _____ inches from any Class 1
conductors?
NFPA 70-760.136(G)
Which of the following environmental conditions is not Air velocity of 400 ft/min
appropriate for the installation of a smoke detector?
NFPA 72-17.7.1.8
Consider the use of a power tool that has a three prong Locate a three prong outlet or use tool with a two prong plug
plug (grounded). The only outlets available are two prong
(ungrounded). What action is appropriate?
OSHA
To make connections with the public switched telephone Off-hook
network in preparation for dialing a telephone number is
known as _____?
NFPA 72-3.3.197
Which of the following is not an acceptable method for Test Publication
performing a smoke entry test of the spot type smoke Optical Fiber
detector? Magnet Test
NFPA 72-Table 14.4.3.2 (17) (7)
Consider ¾" flexible conduit where flexibility is required 3
after installation. The length from the last point where the
raceway is securely fastened shall not exceed _____ feet.
NFPA 70-348.30(A), Exception 2
For smooth ceilings, all points on the ceiling shall have a 0.7 times
detector within a distance equal to _____ the selected
spacing?
NFPA 72-17.6.3.1.1(2)
Fire alarm system documentation is required to have a An input / output matrix
sequence of operation. The diagram used to identify the
sequence of operation is _____?
NFPA 72-7.4.9
Shop drawings shall be drawn to an indicated scale, on Floor
sheets of uniform size, with a plan for each _____?
NFPA 72-7.4.2
Consider the use of grounding electrodes. Rod and pipe 8
electrodes shall not be less than _____ feet in length?
NFPA 70-250.53