Study online at https://quizlet.com/_4e3xa1
1. 4 wires what is the maximum number of 14 AWG RHH conductors
which can be installed in 1/2 rigid metal conduit?
2. 3.5'-48" to the actuator Which of the following would be an appropriate mounting
height for a pull station?
3. 1 flash per second What is the minimum flash rate for a visible notification
device?
4. 90" to the top of the device What is the minimum mounting height for audible notifi-
cation devices?
5. Such that the entire lens is not What is the minimum mounting height for visible notifica-
less then 80" tion devices?
6. Voltage=Current X Resistence What is the formula for Ohm's Law
7. Put your meter in series with the When using your mult-meter to measure, you must:
circuit
8. Semi-annually Waterflow devices shall be tested with that frequency?
9. Annually With what frequency shall ionization smoke detectors be
given a functional test?
10. 24 hours in normal operation, 5 What are the standby power requirements for a proprietary
minutes in alarm signaling system?
11. Shunt type Which of the following is a type of auxiliary protective sig-
naling system?
12. A UL listed central station Remote station signaling systems are permitted to send
A receiver located at an unlisted signals to:
monitoring facility
1/9
, NICET LEVEL 1
Study online at https://quizlet.com/_4e3xa1
A fire department or communica-
tions center
13. 600V Non-power limited fire alarm cable shall have an insulation
rating of:
14. 20,000 CFM HVAC system serving Which of these HVAC systems would require duct detectors
a single floor on supply and return?
15,000 CFM HVAC system serving
3 floors
20,000 CFM HVAC system serving
2 floors
15. Group A, E, F According to the IBC, which of the following use Groups
require visual notification?
16. Every 4 hours Digital Alarm communicator transmitters (DACT) which use
call forwarding to the DACR shall be tested with what fre-
quency?
17. True When connecting 4 wires smoke detectors to a fire alarm
system, the power conductors shall be monitored for in-
tegrity.
18. Smoke detectors shall be permit- Which of the following is true regarding smoke detector
ted to use 30 foot spacing as a spacing?
guide
19. A slope of greater than 1 in 8 A slope ceiling is defined as:
20. Fire alarm control equipment Which of the following is true?
shall be protected with an auto-
matic detector when not in con-
tinuously occupied areas
2/9