ICC CALIFORNIA UST INSPECTOR ACTUAL EXAM
COMPLETE QUESTIONS AND CORRECT ANSWERS
All of the following are required for a facility using
statistical inventory reconciliation as a monitoring
alternative for single wall tanks, EXCEPT
a.Provide minimum data reading to SIR provider so
that the reports can be received within 20 days of
end of data collection period.
b. Conduct a tank integrity test every three years.
c.After inconclusive report have dispenser meters
calibrated.
d. Submit an annual SIR report to the local agency.
......answer.....b.
Conduct a tank integrity test every three years.
,2|Page
CCR; 2646.1; supposed to be every 2 years, not 3 years
All of the following is required to be included in an
UST written monitoring procedure, EXCEPT:
a. The methods and equipment, identified by name and
model
b. The names and titles of the persons responsible for
monitoring the equipment.
c. The name of the emergency coordinator
d. A description of the training necessary for the
operation of the tank system. ......answer.....c. The
name of the emergency
coordinator
,3|Page
CCR; 2632
All of the following are exempt from regulation as an
UST, EXCEPT:
a. A 1000 gallon UST on a farm
b. Drums in basements that contain 55 gallons or less
c. Liquid asphalt tank
d. A bulk field constructed UST ......answer.....d. A bulk
field constructed UST
CCR; 2621
, 4|Page
The local agency inspection is conducted to ensure
that the UST is in compliance with?
a. Title 40 CFR, Parts 280 & 281
b. Health & Safety Code, Chapter 6.11 and 23 CCR,
Chapter 18
c. Title 23, Division 3, Chapter 16, Articles 3 or 4 as
applicable and with all permit conditions
d. Health & Safety Code, Chapter 6.67 and 23 CCR,
Chapter 18 ......answer.....c. Title 23, Division 3,
Chapter 16, Articles 3 or 4 as applicable and with all
permit conditions
CCR; 2712 (e)