Who is responsible for the inspection, testing, maintenance and impairment of a
water based fire protection system? ---------CORRECT ANSWER-----------------The
Property owner or designated representative
Who's responsibility is it to provide accessibility to components of a water based
fire protection system? ---------CORRECT ANSWER-----------------The property owner
or designated representative
Who shall correct or repair deficiencies or impairments found during the
inspection, test and maintenance required by standard? ---------CORRECT
ANSWER-----------------The property owner or designated representative
Who is qualified to preform the corrections and repairs of a water based fire
protection system? ---------CORRECT ANSWER-----------------Qualified maintenance
personal or a qualified contractor
A permanently marked metal or rigid plastic information sign shall be placed at
the system control riser supplying an antifreeze loop, dry system, preaction, or
,auxiliary system control valve? ---------CORRECT ANSWER-----------------An
Information Sign,
Records made during all inspections, tests and maintenance shall be made
available to who upon request? ---------CORRECT ANSWER-----------------The
Authority Having Jurisdiction
All records shall be maintained by? ---------CORRECT ANSWER-----------------The
Property Owner
How long should subsequent records be retained? ---------CORRECT ANSWER-------
----------1 year,
After the testing and reinstallation of plugs and caps for auxiliary drain and test
valves, what action is required? ---------CORRECT ANSWER-----------------Shall be
restored to full operational condition,
To avoid false alarms where a supervisory service is provided the alarm receiving
facility shall be notified by the property owner or designated representative
before? ---------CORRECT ANSWER-----------------conducting any test or procedure
that could result in the activation of an alarm,
,Sprinklers shall be inspected when and how? ---------CORRECT ANSWER---------------
--Shall be inspected from the floor level annually
Sprinklers shall not show signs of the following? ---------CORRECT ANSWER-----------
------leakage; shall be free of corrosion, foreign materials, paint, and physical
damage; and shall be installed in the correct orientation
Sprinklers installed installed in concealed spaces such as above ceilings shall
what? ---------CORRECT ANSWER-----------------Shall not require inspection,
Sprinklers installed in areas that are inaccessible for safety considerations due to
process operations shall be inspected? ---------CORRECT ANSWER-----------------
During each scheduled shutdown
The supply of spare sprinklers shall be inspected when? ---------CORRECT
ANSWER-----------------Annually,
A spare sprinkler wrench shall be required for what? ---------CORRECT ANSWER-----
------------Every type of sprinkler,
, Sprinkler pipe and fittings shall be inspected from where and when? ---------
CORRECT ANSWER-----------------Annually from from the floor level,
Sprinkler Pipe hangers and seismic bracing shall be inspected? ---------CORRECT
ANSWER-----------------Annually from the floor level
Gauges on a wet pipe sprinkler system shall be inspected? ---------CORRECT
ANSWER-----------------Monthly,
Gauges on a dry, preaction system, and deluge systems shall be inspected? ---------
CORRECT ANSWER-----------------Monthly
When the gauge near the compressor is reading higher than the gauge near the
dry pipe valve, the air line shall be what? ---------CORRECT ANSWER-----------------
Taken out of service
Waterflow alarm and supervisory alarm devices shall be inspected? ---------
CORRECT ANSWER-----------------Quarterly
The hydraulic design information sign for hydraulically designed systems shall be
inspected? ---------CORRECT ANSWER-----------------Quarterly