How often shall alarm notification appliances be tested? -
ANSWERS-Every 12 months
We're the outgoing and return conductors enter or exit
notification of clients, the conductors are permitted to run
in the same cable assembly for up to which maximum
distance? - ANSWERS-10 feet?
When a device is inaccessible due to excessive height, such
as an atrium, what it the maximum interval for testing? -
ANSWERS-18 months
When installing a wall-mounted fire telephone appliance to
the public, what is the acceptable maximum mounting
height from the floor? - ANSWERS-66 inches
,Elevator lobby smoke detectors shall be mounted within a
maximum of which distance from the center-line of the
door? - ANSWERS-21 feet
At minimum, when working near power lines with voltage
of 600 volts and lower, an aerial lift operator shall maintain
which distance from the lines? - ANSWERS-10 feet
The use of unprotected EMT shall be permitted under which
conditions? - ANSWERS-when in direct contact with the
earth
According to NFPA 70, what is the maximum unsupported
length of 1/2-inch flexible metallic conduit where flexibility
is required after installation? - ANSWERS-4 1/2 feet
What is the maximum bend (in degrees) permitted in a
conduit run between outlet boxes? - ANSWERS-360 Degrees
If the primary power is disconnected and the fire alarm
system goes into an alarm condition, what is the minimum
acceptable time for secondary power to operate the voice
evacuation systems? - ANSWERS-15 minutes
, A riser room temperature switch should activate when the
temperature falls below which level? - ANSWERS-40 degrees
F
According to NFPA 72, what is the maximum sound pressure
level permitted in a space with notification appliances? -
ANSWERS-110 dBA
What is the minimum interval for testing a single-station
smoke detector in multifamily units? - ANSWERS-Annually
Where should a technician install a detector in relation to
beam that is less than 12 inches deep and less that 8 feet in
center? - ANSWERS-At the bottom of the beam
An existing fire alarm cable in a drop ceiling will be spliced.
which one of the following splice locations will comply with
NFPA 70? - ANSWERS-secured inside a listed box or
enclosure
Which function shall be tested for each newly installed
smoke detector? - ANSWERS-smoke entry?