ELECTRICIAN EXAM
When mounting light fixture supported by EMT over a hot tub protected
by GFCI must have a height of . Not allowed in NYC. - ANSWERS-
How many #10 conductors can be legally installed in a 4"inch square
box, 2"1/8 deep? - ANSWERS-12
When installing receptacles around the pool they should be set back
from the inside wall of not less than 6'ft. - ANSWERS-
What kind of circuit must the sump pump and lights in the elevator pit
be connected to :separate branch CKT/ GFCI line side - ANSWERS-
When using a grounding conductor it should not be smaller than #14
copper insulated solid or stranded. - ANSWERS-
Where practicable a separation of at least 6ft shall be maintained
between communication wires and cables on building and lighting
conductors. - ANSWERS-
When using #12THHN or THWN which are both rated for the 90 degree
and when you look at the table 300.15 what is the maximum overcurrent
END OF
PAGE
1
, NYC MASTER LATEST
ELECTRICIAN EXAM
protection that can be used for general wiring? 20A fuse or circuit
breaker - ANSWERS-
When shall it be permitted to use track lighting with receptacles at each
end in a public bathroom? Not allowed in bathrooms - ANSWERS-
Where a boathouse is using a ramp that is movable because of the water
level changing with the tides. What wiring type of raceway would you
use at hinges? Liquidtight flexible metal conduit (no more that 6'ft) -
ANSWERS-
What is not required to be marked on signaling wire cable ? Voltage -
ANSWERS-
For roads, streets and other areas subject to truck traffic, the minimum
clearance of a 22KV overhead line shall be: 18.5'ft. - ANSWERS-
Mandatory rules of this code are those that identify actions that are
specifically required or prohibited, use the term as: Shall or Shall not -
ANSWERS-
END OF
PAGE
2
, NYC MASTER LATEST
ELECTRICIAN EXAM
What is not listed on a motor disconnect switch? - ANSWERS-
Laboratory approval
Power conductor on poles must have a separation of not less than
30"inches Above from the communication conductors, when the power
is greater than 300V - ANSWERS-
Fuses and circuit breakers shall be permitted to be connected in Parrallel
where they are factory assembled in parallel and listed as a unit. -
ANSWERS-
What is the maximum length of flexible metal conduit allowed in duct or
plenum used for environmental air that is physically connected to
equipment and permitted to be used in ducts or plenum chambers? 4'ft -
ANSWERS-
When are lights permitted to be installed in ducts or plenums used for
environmental air: Enclosed gasket type - ANSWERS-
Electric vehicle equipment locations, when the site is indoors, the
coupling means of the electric vehicle supply equipment shall be stored
END OF
PAGE
3
, NYC MASTER LATEST
ELECTRICIAN EXAM
or located at a height of not less than 18'inches and not more than 4'ft
above the floor level. - ANSWERS-
Electric vehicle supply equipment locations, when the site is outdoors,
the coupling means of the electric vehicle supply equipment shall be
stored or located at a height of not less than 24"inches and not more than
4'ft above the parking surface. - ANSWERS-
What is the minimum distance a wall mounted luminaries that can be
mounted below the surface of water in a pool ? 4"inches - ANSWERS-
The Value in M ohms of a resistor required to discharge a 30 Mfd
capacitor to safe levels, in the time required by the NYC electrical Code,
that has been energized to 650V is most nearly? 10 - ANSWERS-
What diameter of a # 14AWG wire is most nearly? .064"inches -
ANSWERS-
What is the short circuit capacity of a 72 KVA transformer with a 240V
secondary and an impedance of 3%? 10,000A - ANSWERS-