Questions And Correct Answers
The __________ Is Responsible To Maintain Sprinkler Sys. And To Determine
Qualifications.
Owner
Records Of All Inspections And Mx Shall Be Maintained On Premises For A Min. Of
__________ Years.
3
The Building Owner Shall Assign A(N) ____________ To Comply With Requirements.
Impairment Coordinator
Regular Mx And Minor Repairs Not Affecting More Than ________ Floor(S) Are
Considered Planned Removal From Service.
1
Shutdowns Affecting More Than _________ Floor(S) Are Considered Unplanned Out Of
Service Conditions.
1
,Notification To Fdny Is Not Required, Provided System Is Returned To Service Within
______ Hours.
8
For Unplanned Removal From Service, The Cof Holder Shall Immediately Report
Condition To The ___________ And The Fire Dept.
Owner Of The Building
If A Minor Defect Is Observed, It Shall Be Corrected Within _________ Days Or It Will Be
Considered An Impairment.
30
What Does "Oos" Stand For?
Out Of Service
Oos Systems Shall Be Identified By Placing ________ At Fire Dept. Connections, Sys.
Control Valves, And Fire Command Center
Tags
, A _______ Shall Be Required To Post Tags At Main Control Valve And Any Sectional
Valves.
Master Fire Suppression Piping Contractor
__________ Shall Be Posted On The Tag Indicating Both Static And Flow Pressures
Before And After.
Drain Test Results
Green Tags Indicate That __________.
No Impairment Was Found
Green Tags Will Be Placed On The ____________.
Main Control Valve
Systems Partially Or Fully Out Of Service Shall Have A ____________ Tag Placed On The
Main Control Valve.
Red
A _________ Disc Of 8-9 Inches Shall Be Placed On Connections To Indicate The System
Is Fully Out Of Service.
White