cylinder - CORRECT ANSWER-Supply tank containing high pressure gases or
gas mixtures at pressures that can be in excess of 2000 psig.
producer - CORRECT ANSWER-The device(s) that generates the flow and
suction required for vacuum and plume evacuation systems to operate.
piping distribution system - CORRECT ANSWER-Pipeline network assembly of
equipment that starts at and includes the source valve, warning systems, and all
other components including the station outlets/inlets.
scavenging - CORRECT ANSWER-The evacuation of exhaled mixtures of oxygen
and nitrous oxide.
container - CORRECT ANSWER-Low pressure, vacuum-insulated vessel
containing gases in liquid form.
True - CORRECT ANSWER-A bulk system with a storage capacity of more than
20,000 cu ft of inert gas is a Bulk Inert Gas System.
,True - CORRECT ANSWER-The branch lines are those sections or portions of
the piping system that serve a room or group of rooms on the same story of the
facility.
25 ppm - CORRECT ANSWER-The ppm gaseous hydrocarbons in the medical air
system shall be less than?
32 degrees F - CORRECT ANSWER-At any level of demand, the medical air
dryers shall provide air with a dew point below this temperature?
medical air compressors - CORRECT ANSWER-Which of the following is NOT
permitted to have the system supply source located outside?
A. vacuum pumps
B. manifolds for gas cylinders
C. instrument air compressors
D. medical air compressors
duplexed - CORRECT ANSWER-Regulators, filters, and dryers shall be sized to
meet the peak calculated demand. The piping format for these items shall be at a
minimum?
,Authority Having Jurisdiction (AHJ) - CORRECT ANSWER-They can allow an
existing system, which is not in compliance with the NFPA 99 Code to remain in
service.
pressure regulator - CORRECT ANSWER-Medical air supply systems operating
at different pressures shall be provided with?
unusable - CORRECT ANSWER-The removal of the outlet connection on a
cryogenic liquid container will cause the container to become?
laboratory - CORRECT ANSWER-A building, space, room, or group of rooms
intended to serve activities involving procedures for investigation, diagnosis, or
treatment in which flammable, combustible, or oxidizing materials are to be used.
20 degrees F - CORRECT ANSWER-Carbon dioxide and nitrous oxide cylinders
shall be kept from reaching temperatures below _____.
-22 degrees F - CORRECT ANSWER-The master alarm shall activate when the
instrument air compressor dew point temperature exceeds _____.
, Category 1 - CORRECT ANSWER-In this space, alarm sensors shall be installed
on the patient's side of each individual zone valve box.
patient care vicinity - CORRECT ANSWER-The locations within 6' of the
patient's bed and 7'-6" from the ceiling, where examinations take place?
high water level - CORRECT ANSWER-Where liquid ring compressors for
medical air are used, the air receiver shall have a local alarm which will shut down
the system due to?
Category 4 Space - CORRECT ANSWER-An area where failure of a system is not
likely to cause any physical impact on a patient.
hyperbaric facility - CORRECT ANSWER-Building or structure, used to house
hyperbaric chambers for medical applications and procedures at pressures above
normal atmospheric pressure.
area alarm - CORRECT ANSWER-The warning system that provides a
continuous visible and audible vigilant watch on Category 1 & Category 2 piping
systems.