S-12 Citywide Sprinkler Systems, S12
Sprinkler Test 2026 | Brand New
Questions And Verified Solutions
the __________ is responsible to maintain sprinkler sys. and to determine
qualifications. - correct-answer -owner
records of all inspections and mx shall be maintained on premises for a min. of
__________ years. - correct-answer -3
the building owner shall assign a(n) ____________ to comply with requirements. -
correct-answer -impairment coordinator
regular mx and minor repairs not affecting more than ________ floor(s) are
considered planned removal from service. - correct-answer -1
, 2
shutdowns affecting more than _________ floor(s) are considered unplanned out
of service conditions. - correct-answer -1
notification to fdny is not required, provided system is returned to service within
______ hours. - correct-answer -8
for unplanned removal from service, the cof holder shall immediately report
condition to the ___________ and the fire dept. - correct-answer -owner of the
building
if a minor defect is observed, it shall be corrected within _________ days or it will
be considered an impairment. - correct-answer -30
what does "oos" stand for? - correct-answer -out of service
oos systems shall be identified by placing ________ at fire dept. connections, sys.
control valves, and fire command center - correct-answer -tags
, 3
a _______ shall be required to post tags at main control valve and any sectional
valves. - correct-answer -master fire suppression piping contractor
__________ shall be posted on the tag indicating both static and flow pressures
before and after. - correct-answer -drain test results
green tags indicate that __________. - correct-answer -no impairment was found
green tags will be placed on the ____________. - correct-answer -main control
valve
systems partially or fully out of service shall have a ____________ tag placed on
the main control valve. - correct-answer -red
a _________ disc of 8-9 inches shall be placed on connections to indicate the
system is fully out of service. - correct-answer -white
a ________ disc of 8-9 inches shall be placed on connections to indicate the
system is partially out of service. - correct-answer -blue
, 4
the impairment coordinator will notify the ___________ carrier, central station
and occupants. - correct-answer -insurance
prior to returning a sys. to service, the ___________ shall ensure that necessary
tests and inspections are conducted. - correct-answer -impairment coordinator
glycerin not greater than _________ percent or glycol not greather than ________
percent shall be used to protect from freezing. - correct-answer -50, 40
the cof number and signature of cof holder shall be posted near the
____________. - correct-answer -main control valve
__________ shall be readily available to any representative of the fire dept. these
are to be maintained on site for 3 years. - correct-answer -records
failure to make inspections may result in __________ of the cof and court
proceedings. - correct-answer -revocation