for Health Care Facility Managers Exam
Questions & Correct Answers Instant
Download Pdf
1. A facility manager is reviewing a renovation plan that involves the installation of a
new medical gas headwall in a patient care suite. Under the 2012 edition of NFPA 99,
which entity is ultimately responsible for certifying that the medical gas system
installation is safe for use prior to patient occupancy?
A) The installing contractor
B) The facility’s Medical Director
C) The Authority Having Jurisdiction (AHJ)
D) The facility’s Qualified Medical Gas Installer
Correct Answer: C) The Authority Having Jurisdiction (AHJ)
Rationale: NFPA 99 (2012) Section 5.1.14.2 requires that the AHJ (which in a healthcare
facility is often the facility management or a designated third party) certify that the
medical gas system has been inspected, tested, and is in compliance with the standard
before it is placed into service. While the contractor (A) installs and the medical gas
installer (D) verifies, the ultimate responsibility for certification and acceptance lies with
the AHJ.
2. A fire door in a corridor leading to an exit stairwell fails to self-close after being
opened. According to NFPA 101 (Life Safety Code), this represents a violation of which
,classification of door required for a means of egress?
A) Fire door
B) Smoke door
C) Fire-protection-rated door
D) Self-closing door
Correct Answer: D) Self-closing door
Rationale: While the door is likely a fire-rated assembly, the specific requirement in
NFPA 101 Section 7.2.1.8.2 mandates that doors in a means of egress, specifically those
in corridors and smoke barriers, must be self-closing or automatic-closing. The failure to
self-close directly violates the operational requirement of the means of egress,
regardless of the rating of the door itself.
3. During a routine inspection, you discover that a fire sprinkler head in a hospital
storage room has been painted by the maintenance staff. What is the most immediate
and correct course of action?
A) Document the painting as a "finish" change, which is permitted by NFPA 25.
B) Remove the paint using a chemical paint stripper and note the cleaning in the
records.
C) Replace the sprinkler head with an equivalent new head.
D) Conduct a flow test to ensure the paint did not clog the orifice.
Correct Answer: C) Replace the sprinkler head with an equivalent new head.
Rationale: NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-
Based Fire Protection Systems, prohibits the painting of sprinkler heads except by the
manufacturer. Painting can corrode components, insulate the thermal element, and
prevent proper operation. The only acceptable remedy is replacement.
,4. A facility is classified as a "Business Occupancy" under NFPA 101 but contains a small
outpatient clinic offering same-day surgery. What reclassification is required for the
portion of the building containing the surgery suite?
A) Business Occupancy remains applicable as long as patients are not admitted for 24
hours.
B) Ambulatory Health Care Occupancy
C) Health Care Occupancy
D) Institutional Occupancy
Correct Answer: B) Ambulatory Health Care Occupancy
Rationale: NFPA 101 defines Ambulatory Health Care Occupancy as buildings or
portions thereof used to provide medical treatment on an outpatient basis where four
or more patients are rendered incapable of self-preservation at the same time. Same-
day surgery patients under anesthesia typically meet this definition, necessitating
reclassification for that portion of the building, which triggers more stringent
requirements (e.g., sprinkler coverage).
5. In the context of Interim Life Safety Measures (ILSM), what is the primary distinction
between an "Impaired" fire protection system and an "Out of Service" system?
A) Impairment is planned; Out of Service is an emergency.
B) There is no distinction; the terms are synonymous.
C) Impairment means the system is operational but deficient; Out of Service means it is
completely non-functional.
D) Impairment requires a fire watch; Out of Service requires system replacement.
Correct Answer: C) Impairment means the system is operational but deficient; Out
of Service means it is completely non-functional.
Rationale: While often used interchangeably in common language, NFPA and TJC
standards differentiate these. An "impairment" typically refers to a system that is not
, fully operational (e.g., a closed valve, partial outage). "Out of service" implies total
system failure or deactivation. Both require ILSM, but the level of mitigation (e.g., fire
watch frequency) often intensifies when a system is fully out of service.
6. A generator set in a healthcare facility fails its monthly load bank test because the
coolant temperature exceeded manufacturer limits. According to NFPA 99, what is the
required follow-up action?
A) No action is required if the generator started and transferred load.
B) The failure must be documented, and repairs must be made prior to the next monthly
test.
C) The generator must be immediately replaced.
D) The facility must file a waiver with the state health department.
Correct Answer: B) The failure must be documented, and repairs must be made
prior to the next monthly test.
Rationale: NFPA 99 (2012) Section 6.4.4.1.1.2 requires that if a generator fails to perform
to manufacturer specifications during a test, the deficiency must be corrected and
documented. The equipment does not need to be replaced (C) unless irreparable, and
filing a waiver (D) is not the standard procedure for a failed test.
7. In a medical office building classified as Business Occupancy, where is the required
location for the portable fire extinguisher relative to a Class B fire hazard (flammable
liquids storage)?
A) Within 30 feet of travel distance
B) Within 50 feet of travel distance