Questions with Correct Answers|
Latest Update
which disinfectant would work best against Cryptosporidium
Ozone
The pH of a Water sample Is greater than the PHs so the Langelier index
indicates the water is scale forming
When water high in calcium bicarbonate is softened by ion exchange
Sodium Bicarbonate remains in the product water
A bypass valve would be used with a
gate valve
Where ground frost is expected the riser pipes in a meter pit should be atleast
how far away from any wall of the meter box to prevent freezing
1-2 inches
,which type of pipe joint is available in both bolted and bolt less flexible pipe
joint designs
Ball and Socket Joint
which type of pipe joint permits flexible pipe alignment is inexpensive to
manufacture and is easy to assemble
push on joint
new polyvinyl chloride pipe has a c-value of about
150+
which type of valve would be particularly useful for throttling the flow of
corrosive liquids
pinch valve
Water meter pits are usually used in
cold climates
fuel oil will permeate which type of pipe
polyethylene pipe
An ion exchange softener is treating a flow rate of 125 gpm. what is the
operating time in hours if the softener unit treats 297000 gallons before it
requires regeneration?
39.6 hr
,in describing pump operation what type of curve shows the relationship
between power and capacity
P-Q curve
What is Head Loss
energy used by water when moving from point to point
Static Suction Lift
Difference in water placement
What is Power
Work done in a given time
if a water system collects at least 40 samples per month for the analyses of total
coliforms, what percentage of total coliform samples are acceptable for the
system to remain in compliance with the maximum contaminant level for total
coliforms
, no more than 5%
water systems are required to achieve at least________ removal and or
inactivation of viruses between a point where the raw water is not subject to
recontamination by surface water runoff and a point downstream before or at
the first customer.
4 log
where are the sampling points located for required samplings of organics
(except THMs) in a community water system
entry points to the distribution system
where are the sampling points located for required sampling of natural
radionuclides in a community water system
each entry point to the system
continuous chlorine residual monitoring is required where the water enters the
distribution system under the SWTR when the
population served is >3300 people.