Sprinkler water storage containers shall be supervised to indicate what the water
temperature drops to which level?
Choose an answer
1 30 degrees F 2 50 degrees F
3 40 degrees F 4 60 degrees F
Don't know?
When a device is inaccessible due to excessive height, 18 months
such as an atrium, what it the maximum interval for
testing?
When installing a wall-mounted fire telephone appliance 66 inches
to the public, what is the acceptable maximum mounting
height from the floor?
, Elevator lobby smoke detectors shall be mounted within 21 feet
a maximum of which distance from the center-line of the
door?
At minimum, when working near power lines with voltage 10 feet
of 600 volts and lower, an aerial lift operator shall
maintain which distance from the lines?
The use of unprotected EMT shall be permitted under when in direct contact with the earth
which conditions?
According to NFPA 70, what is the maximum unsupported 4 1/2 feet
length of 1/2-inch flexible metallic conduit where
flexibility is required after installation?
What is the maximum bend (in degrees) permitted in a 360 Degrees
conduit run between outlet boxes?
If the primary power is disconnected and the fire alarm 15 minutes
system goes into an alarm condition, what is the minimum
acceptable time for secondary power to operate the
voice evacuation systems?
A riser room temperature switch should activate when the 40 degrees F
temperature falls below which level?
According to NFPA 72, what is the maximum sound 110 dBA
pressure level permitted in a space with notification
appliances?
What is the minimum interval for testing a single-station Annually
smoke detector in multifamily units?
Where should a technician install a detector in relation to At the bottom of the beam
beam that is less than 12 inches deep and less that 8 feet
in center?
An existing fire alarm cable in a drop ceiling will be secured inside a listed box or enclosure
spliced. which one of the following splice locations will
comply with NFPA 70?
Which function shall be tested for each newly installed smoke entry?
smoke detector?
An 180 foot long corridor is 10 feet wide, with a smooth 10 6 heat detectors
foot ceiling, interrupted by 4-inch beams spaced every
10 feet. How many heat detectors with a listed 30 foot
spacing are required?
At which height must cables be physically protected 7 feet
when being installed within an exposed ceiling?