NICET 1
Save
Students also studied
nicet level 1 questions Nicet level 1 Study Guide questions NICET Level 1 Fire Alarm Systems NICET
13 terms 148 terms 119 terms 86 terms
pbellacero94 Preview mwstabnow Preview waddymichael Preview ben
If the total resistance in the above circuit is 571 ohms, 21 milliamps
what is the total current?
What type of fire extinguisher would you use for fire Class D
where there metals such as or titanium?
What type of detector would be best suited for the large Projected beam
public areas of multi-story indoor shopping mall with
high ceilings?
Record keeping requirements include Select all that The records must be permanent.
apply The owner shall be required keep all permanent records on paper electronic
media for minimum of five years.
A copy of ste-specific software shall be kept in non-erasable format, such as a CD
ROM.
Permanent records include as-built drawings, system operation and maintenance
manuals written sequence operation, and inspection and testing documentation
NFPA 72 Sec. 14.6
You can remove safety guards from what type of tools/ None
machinery.
What is the total resistance in the circuit above 571 ohms
When using an air sampling smoke detector, the 120 seconds
maximum transport time from the sample port to the
detector can be no more than ____ seconds
,NFPA states that all testing and maitenance should be BSEE
fine by qualified personnel. which of the following does
not make a person qualified.
NICET Certification
Factory Training
Bachelor Degree in Electrical Engineering (BSEE)
Local authority Certification
Which procedure should be followed to safely move a Immobilize the leg
person with s suspected fractured leg.
Sterilize the area around the suspected fractured
Immobilized the leg
place the leg in traction
Administer sick treatment to the victim
Bandage the leg
Sound level measurement are taken per a standard ANSI
published by
Never move an interesting person unless There is a fire
Select all that apply There are explosives
They have a spinal injury
There is a fire
There are explosives involved
They are bleeding
Devices that cannot be tested per the frequencies Table 18
14.4.3.2 due to safety concerns can be inspected at
scheduled Asian people if approved by the AHJ.
However, the extended period cannot exceed ____
months
Dates does for performing electrical work must be non- False, slip resistance not required for elec. work
conductive and skip resistance
T or F
Protective gloves are worn: when sharp edges or splinters are involved
when dealing with elevated temperature s of material or equipment.
NFPA 72 does require annual testing if all restorable fixed 5
temp heat detectors, but 2 on each circuit shall be tested
annually. However, each detector must be tested at least
every ___ yrs.
The secondary power supply must be capable of 10 seconds
assuming the maximum load of protected premises
system within ____.
The respirator is a device which removes solid particles False, that's called a filter
from the airs, such as dust, mold, bacteria and pollen.
, On a level banned ceiling, which initiating devices is Spot type smoke detector
allowed to be using smooth ceiling spacing when the
beam depth is less than 10% if the ceiling height.
When you are installing a new fire alarm system, which of NFPA 72 and 70
the following code would you refer to? select all that
apply
NFPA 101
NFPA 72
NFPA 70
IBC
If a household has multiple station alarm devices When one device goes into alarm, they all go into alarm
They must be connected to a fire alarm control panel
When one device yours into alarm, they all go into alarm
One of the devices shall be the matter device
They just ask be smoke detectors
A non restorable heat detector Must be resolved after actuating
Must be manually reset
Must be resolved start actuating
Maintains the highest temperature it is exposed to
Is not permitted by code
Which of the following statement are true in regards to A B And C
smoke detectors sensitivity
Select All Apply
Sensitivity is measured in percent per for obscuration
Sensitivity must be marked on the smoke detector
If the sensitivity is adjustable, the minimum setting cannot
be less than 0.6
If the sensitivity is adjustable, the minimum setting cannot
be less than 6.0
A manual fire alarm box must be red in color unless The application prohibits the use of plastic or red paint
Calculate 376.2 x 0.0022 (Rounding to the nearest ten 0.8276
thousandth)
What is the max number of 14 gauge wire which can be 15
pulled straight through a 4"X2 1/8" square trade size metal
elec box
The circuit breaker supplying to the fire alarm control False
panel must be ground fault circuit interrupter
T or F
If a defect is found when inspecting a fire alarm system. 24 hours
The owner shall be notified in writing within?
A projected beam sensor uses which of the following Light obscuration
operating principles?