Nicet level 1 Study Guide questions
Save
Students also studied
NICET Fire Alarm Level 1 NICET Level 1 Fire Alarm Systems nicet level 1 questions NICET 1
107 terms 119 terms 13 terms 49 terms
jesus_cortez79 Preview waddymichael Preview pbellacero94 Preview Me
Practice questions for this set
Learn 1 /7 Study using Learn
When a modification is made to a fire alarm system after the initial installation, the
modification shall be recorded on a revised version of the original completion
documents. The revised record of completion document shall include ________.
Choose an answer
1 The warranty expiration date 2 The installer's name
3 The revision date 4 The original installation date
Don't know?
When testing a water level supervisory switch serving a rises or falls over 3 inches
pressure tank a signal shall indicate if the water level
_____________from the required level
(NFPA 72, Table 14.4.3.2 17 ( j) (4)
, If combination audible/visible appliances are installed the the visible appliance
location of the installed appliance shall be determined
by the requirements of _______.
(Nfpa 72 18.4.8.1)
What is the maximum number of 12 gauge THHN wires 26
that can be installed in 1" EMT?
(Nec Annex C tables)
Two resistors are connected in parallel. R1 = 300 Ohms, 150 ohms
R2 = 300 Ohms. What is their equivalent resistance?
A Room is 200' long and 150' wide and the 8' high ceiling 12
is smooth and flat. A spot type heat detector has been
selected that is listed for a 50' maximum spacing between
detectors. According to NFPA 72 how many detectors
will be needed to protect this room?
x =
According to NFPA 72 the minimum number of restorable Two detectors or more on each initiating device circuit
fixed temperature spot type heat detectors that must be
tested during each annual test is?
(NFPA 72 14.4.4.5.1)
According to NFPA 72 how many spot type heat 6
detectors are required for a space that is 80' long and 55
floor wide with a smooth 10' ceiling? the detector is listed
for a maximum space between detectors of 30'
What color code requirement for a spot type heat White (NFPA 72, Table 17.6.2.1)
detector rated at 200 F ゚
Unless otherwise recommended by the manufacturers 10 years from the day-of manufacture. (NFPA 72, 14.4.7.1)
published instructions single and multiple stations smoke
alarms installed in one and 2 family dwellings shall be
replaced every
Fire alarm cables are permitted to be strapped to conduit False (NEC 760.143)
to support the cable
Where non power limited wiring is installed exposed it 7' ft
must be mechanically protected within_____of the finished
floor
Fire-Warning equipment to be installed in residential ANSI S3.41
occupancies shall produce the audible emergency
evacuation signal described in