Maine State Journeyman, Oil test, Fuel Code & Plumbing Exam Complete Exam Study Questions with 100% Correct Answers (Expert Graded A+) Brand New Version | Guarantee Pass 1. How many apprentices can a journeyman directly supervise? - ANSWER 2 apprentices - MFC 3.2.6 2. Can a licensed Journeyman perform a cleaning on a wood/oil combination unit without direct supervision? - ANSWER If they have an apprentice solid fuel license MFC 3.2.7 3. Who is responsible for ensuring repairs or the chimney is lined within the 90 days? - ANSWER The licensee. MFC 8.5.4 4. When is a heat loss required? - ANSWER New installations, the heat loss must be conducted and a copy must be retained by the licensee. MFC 8.5.5.1 5. Prior to a boiler replacement a ____ or a _____ must be conducted before replacement of an existing system. - ANSWER Heat loss or load calculation. MFC 8.5.5.2 6. Who must maintain a copy of a heat load calculation? - ANSWER The licensee. MFC 8.5.5.2 7. The low water cutoff must be located where? - ANSWER At a level recommended by the manufacturer, but in no case shall the low water cutoff be installed below the crown sheet. MFC 8.6.2 8. Boiler and safety control or devices may have no ______ installed between the _____ and the ______. - ANSWER Valves or obstructive devices; boiler and safety device/control. MFC 8.6.4 9. When outside tanks are used a _____ must be installed where the supply line enters (inside) the building - ANSWER Thermally operated shutoff valve. MFC 8.7.1.1.1 10.When inside tanks are installed in a separate room the thermally operated valve must be________? - ANSWER Installed where the line enters the room where the appliance is located. MFC 8.7.1.1.2 11.A check valve may be installed in the supply line but no _____ or _____ may be installed in the return line connected to a burner or pump. - ANSWER Valve or obstruction. MFC 8.7.1.2 12.What must be done if a thermally operated valve larger than 1/2" must be used? - ANSWER Obtain written approval of a board inspector, prior to installation. MFC 8.7.2 13.An oil supply or return line under cement, sub-floor or earth surface must be _____ and without _____? - ANSWER Continuous; without any splices MFC 8.8.1 14.All copper oil supply and return lines must be encased in a _____ such as PVC ENT or be _____ or other approved materal and must be _____? - ANSWER Continuous piece of non-metallic liquid tight conduit; coated coper tubing; secured in order to prevent physical damage. MFC 8.8.2 15.The end of the conduit for an oil supply or return line shall not exceed _____ from any fitting, except the connection at the fuel tank and at the pump located at the burner shall not exceed _____? - ANSWER 2 inches ; 6 inches MFC 8.8.2 16.In order to avoid undetected oil leaks under floors the conduit must be _____ than the supply and return lines. The ends of the conduit must penetrate the cement or earth surface a minimum of _____? - ANSWER One pipe size larger; 2 inches above grade. MFC 8.8.2 17.Coated copper tubing must have ______ installed at the tank when _____? - ANSWER An OSV or PRV valve; used underground. MFC 8.8.3 18.Whenever an outlet of an oil supply tank is located more than _____ the burner a _____ or _____ valve is required? - ANSWER 4 feet above; OSV or PRV MFC 8.8.4 19.A graduate of an 160 hour Maine fuel board approved course on oil burning equipment may set for the journeyman exam when? - ANSWER Upon successful completion of the requisite education, prior to completing the apprenticeship 20.The Maine fuel board adopts NFPA 31 and NFPA 211, which edition? - ANSWER NFPA 31 2011 edition and NFPA 211 2013 edition. MFC 6.1.2 and 6.1.13 21.What are the two chapters and sections of NFPA 31 that Maine does not adopt? - ANSWER Chapter 7 section 7.12 and Chapter 7 section 7.3.1 MFC 6.2.1 22.What does Maine fuel board say about inspecting chimneys as required by NFPA 211 chapter 14?` - ANSWER The Maine fuel board does not adopt chapter 14 of NFPA 211. MFC 6.2.6.4.3 23.All work must be conducted, installed and completed in a ______? - ANSWER Neat and professional manner reflecting a minimum level of workmanship. MFC 8.2 24.When performing any service work on a customer's heating system, the licensee must notify the homeowner of? - ANSWER Any code violations and make recommendations to address them. MFC 8.4.2 25.When performing an annual tune-up on a heating system a combustion efficiency test must be? - ANSWER Conducted and a copy of the results must be posted on site. MFC 8.4.3 26.When installing a furnace, direct fired water heater or boiler what must be done prior to placing it in service? - ANSWER The total installation must be brought into compliance with the requirements of NFPA 31 and all other rules of the Maine fuel board. MFC 8.5.1 27.Outside oil tank supports shall not be? - ANSWER Wood, oil tanks shall not be installed on wood or other combustible surfaces or supports. MFC 8.10.1

Meer zien Lees minder
Instelling
Maine State Journeyman
Vak
Maine State Journeyman

Voorbeeld van de inhoud

Maine State Journeyman, Oil test, Fuel
Code & Plumbing Exam Complete Exam
Study Questions with 100% Correct
Answers (Expert Graded A+) <Brand New
Version> | Guarantee Pass

1. How many apprentices can a journeyman directly supervise? - ANSWER 2
apprentices - MFC 3.2.6


2. Can a licensed Journeyman perform a cleaning on a wood/oil combination
unit without direct supervision? - ANSWER If they have an apprentice solid
fuel license MFC 3.2.7


3. Who is responsible for ensuring repairs or the chimney is lined within the 90
days? - ANSWER The licensee. MFC 8.5.4


4. When is a heat loss required? - ANSWER New installations, the heat loss
must be conducted and a copy must be retained by the licensee. MFC 8.5.5.1


5. Prior to a boiler replacement a ____ or a _____ must be conducted before
replacement of an existing system. - ANSWER Heat loss or load
calculation. MFC 8.5.5.2


6. Who must maintain a copy of a heat load calculation? - ANSWER The
licensee. MFC 8.5.5.2

,7. The low water cutoff must be located where? - ANSWER At a level
recommended by the manufacturer, but in no case shall the low water cutoff
be installed below the crown sheet. MFC 8.6.2


8. Boiler and safety control or devices may have no ______ installed between
the _____ and the ______. - ANSWER Valves or obstructive devices; boiler
and safety device/control. MFC 8.6.4


9. When outside tanks are used a _____ must be installed where the supply line
enters (inside) the building - ANSWER Thermally operated shutoff valve.
MFC 8.7.1.1.1


10.When inside tanks are installed in a separate room the thermally operated
valve must be________? - ANSWER Installed where the line enters the
room where the appliance is located. MFC 8.7.1.1.2


11.A check valve may be installed in the supply line but no _____ or _____
may be installed in the return line connected to a burner or pump. -
ANSWER Valve or obstruction. MFC 8.7.1.2


12.What must be done if a thermally operated valve larger than 1/2" must be
used? - ANSWER Obtain written approval of a board inspector, prior to
installation. MFC 8.7.2


13.An oil supply or return line under cement, sub-floor or earth surface must be
_____ and without _____? - ANSWER Continuous; without any splices
MFC 8.8.1


14.All copper oil supply and return lines must be encased in a _____ such as
PVC ENT or be _____ or other approved materal and must be _____? -

, ANSWER Continuous piece of non-metallic liquid tight conduit; coated
coper tubing; secured in order to prevent physical damage. MFC 8.8.2


15.The end of the conduit for an oil supply or return line shall not exceed _____
from any fitting, except the connection at the fuel tank and at the pump
located at the burner shall not exceed _____? - ANSWER 2 inches ; 6
inches MFC 8.8.2


16.In order to avoid undetected oil leaks under floors the conduit must be _____
than the supply and return lines. The ends of the conduit must penetrate the
cement or earth surface a minimum of _____? - ANSWER One pipe size
larger; 2 inches above grade. MFC 8.8.2


17.Coated copper tubing must have ______ installed at the tank when _____? -
ANSWER An OSV or PRV valve; used underground. MFC 8.8.3


18.Whenever an outlet of an oil supply tank is located more than _____ the
burner a _____ or _____ valve is required? - ANSWER 4 feet above; OSV
or PRV MFC 8.8.4


19.A graduate of an 160 hour Maine fuel board approved course on oil burning
equipment may set for the journeyman exam when? - ANSWER Upon
successful completion of the requisite education, prior to completing the
apprenticeship


20.The Maine fuel board adopts NFPA 31 and NFPA 211, which edition? -
ANSWER NFPA 31 2011 edition and NFPA 211 2013 edition. MFC 6.1.2
and 6.1.13

, 21.What are the two chapters and sections of NFPA 31 that Maine does not
adopt? - ANSWER Chapter 7 section 7.12 and Chapter 7 section 7.3.1 MFC
6.2.1


22.What does Maine fuel board say about inspecting chimneys as required by
NFPA 211 chapter 14?` - ANSWER The Maine fuel board does not adopt
chapter 14 of NFPA 211. MFC 6.2.6.4.3


23.All work must be conducted, installed and completed in a ______? -
ANSWER Neat and professional manner reflecting a minimum level of
workmanship. MFC 8.2


24.When performing any service work on a customer's heating system, the
licensee must notify the homeowner of? - ANSWER Any code violations
and make recommendations to address them. MFC 8.4.2


25.When performing an annual tune-up on a heating system a combustion
efficiency test must be? - ANSWER Conducted and a copy of the results
must be posted on site. MFC 8.4.3


26.When installing a furnace, direct fired water heater or boiler what must be
done prior to placing it in service? - ANSWER The total installation must
be brought into compliance with the requirements of NFPA 31 and all other
rules of the Maine fuel board. MFC 8.5.1


27.Outside oil tank supports shall not be? - ANSWER Wood, oil tanks shall
not be installed on wood or other combustible surfaces or supports. MFC
8.10.1

Geschreven voor

Instelling
Maine State Journeyman
Vak
Maine State Journeyman

Documentinformatie

Geüpload op
30 maart 2026
Aantal pagina's
57
Geschreven in
2025/2026
Type
Tentamen (uitwerkingen)
Bevat
Vragen en antwoorden

Onderwerpen

$11.99
Krijg toegang tot het volledige document:

Verkeerd document? Gratis ruilen Binnen 14 dagen na aankoop en voor het downloaden kun je een ander document kiezen. Je kunt het bedrag gewoon opnieuw besteden.
Geschreven door studenten die geslaagd zijn
Direct beschikbaar na je betaling
Online lezen of als PDF

Maak kennis met de verkoper
Seller avatar
DrSammuel

Maak kennis met de verkoper

Seller avatar
DrSammuel TeachmeTutor
Volgen Je moet ingelogd zijn om studenten of vakken te kunnen volgen
Verkocht
4
Lid sinds
4 maanden
Aantal volgers
0
Documenten
655
Laatst verkocht
2 weken geleden
Turning Preparation into Achievement.

Welcome to my study resource hub! This account provides high-quality exam papers with clear and detailed elaborations designed to help students fully understand each topic and pass with confidence.

0.0

0 beoordelingen

5
0
4
0
3
0
2
0
1
0

Recent door jou bekeken

Waarom studenten kiezen voor Stuvia

Gemaakt door medestudenten, geverifieerd door reviews

Kwaliteit die je kunt vertrouwen: geschreven door studenten die slaagden en beoordeeld door anderen die dit document gebruikten.

Niet tevreden? Kies een ander document

Geen zorgen! Je kunt voor hetzelfde geld direct een ander document kiezen dat beter past bij wat je zoekt.

Betaal zoals je wilt, start meteen met leren

Geen abonnement, geen verplichtingen. Betaal zoals je gewend bent via iDeal of creditcard en download je PDF-document meteen.

Student with book image

“Gekocht, gedownload en geslaagd. Zo makkelijk kan het dus zijn.”

Alisha Student

Bezig met je bronvermelding?

Maak nauwkeurige citaten in APA, MLA en Harvard met onze gratis bronnengenerator.

Bezig met je bronvermelding?

Veelgestelde vragen