All connections within Category 1 medical gas shall be
___________ to prevent cross-connection with other piping
systems. - ANSWERS-gas specific
Where operating pressure are above 185 psi, - ANSWERS-
type K ASTM B819 shall be used
During and after installation, openings in the piping system
shall be kept - ANSWERS-plugged or capped
Category 3 oxygen piping systems shall be not less than
_________ size - ANSWERS-3/8 nps
,Where dissimilar metals, such as copper and bronze or
brass, are being brazed, the flux shall be worked over the
surfaces to be brazed using a - ANSWERS-stiff bristle brush
The medical air quality shall be monitored ______________
of the medical air regulators and ________________ of the
piping system. - ANSWERS-downstream, upstream
Area alarm panels for medical/surgical vacuum systems
shall indicate if the vacuum in the area drops to or below
____________ gauge HgV. - ANSWERS-12
Medical gas and vacuum piping vertical risers shall be
supported, every floor, but not to exceed - ANSWERS-15 ft
Maximum support spacing for 1 inch medical gas piping
shall be - ANSWERS-8ft
What System is used to capture the gases and carry them
away from anesthesia or analgesia equipment? - ANSWERS-
Waste anesthetic gas disposal, or WAGD
, An activities system or equipment whose failure is not likely
to cause injury to patients, staff, or visitors but can cause
discomfort shall be designed to meet which category? -
ANSWERS-CAT 3
A ______ Device is used for connecting the outlets of one or
more gas cylinders to the central piping systems. -
ANSWERS-Manifold
What is a pneumatic terminus of a piped gas system for
other than critical, continuous duty, nonflammable medical
life support-type gases? - ANSWERS-Service outlet.
Medical support gas, nitrogen or instrument air is used to
operate what? - ANSWERS-Medical-surgical tools, air-driven
booms, pendants
What is not part of a typical Cat. 1 medical vacuum system?
- ANSWERS-Patient Lead
An oxygen-enriched atmosphere is the concentration of
oxygen that exceeds ______ percent by volume. - ANSWERS-
23.5%