• Which of the following shall be done when conducting tests in lead-acid type
batteries -✓✓Annually conduct a discharge test with the charger disconnected
while conducting a load test with full alarm load or an artificial load,
• Area of refuge two-way communication systems are required to be tested in
which of the following three ways -✓✓Verify Receipt of visual and audible signal
at the transmitting and receiving unit, respectively
• How often shall secondary power supply be tested? -✓✓Annually
• How often are video image smoke and fire detectors required to be inspected? -
✓✓Annually
• Which two of the following are true regarding acceptable test plans? -✓✓Shall be
documented with the testing records, shall be written to clearly establish the scope
of the testing for the fire alarm or signaling system.
• How often shall fire optic cable connections be inspected? -✓✓Annually
• How many years after the initial installation shall all fixed temperature non
restorable line type detectors be replaced or have 2 per 100 laboratory tested? -
✓✓20 Years
• How often are digital alarm communicator transmitters required to be inspected?
-✓✓Annually
• How are rate of rise heat detectors tested? -✓✓Heat gun or something similar
• What must be done when using a multimeter to measure current? -✓✓Put the
meter in series with the circuit (Pulling negative wire and replacing it with
voltmeter to read current)