SCRIPT FINAL PAPER 2026 FULL
SOLUTION QUESTIONS AND ANSWERS
●● Dental vacuum and scavenging components of a medical gas system
are used for which of the following purposes? Answer: Removal of
anesthetic gas only
●● Who is the individual responsible for reviewing all inspection and
testing reports prior to the use of new, additional, renovated, or
temporary medical gas and vacuum installations? Answer: Responsible
facility authority
●● When storing positive pressure cylinders in an outdoor enclosure, the
enclosure shall meet which of the following requirements? Answer: Be
well drained protecting cylinders from the soil
●● A Central Supply System with a storage capacity of more than 3200
pounds at normal temperature and pressure best describes which system?
Answer: Bulk Nitrous Oxide Central Supply
●● Where liquid ring compressors are used, air receivers shall be
equipped with a high water level
sensor that activates a(n)________ alarm indicator Answer: Local
, ●● Instrument air systems shall activate the alarm systems when the dew
point at system pressure exceeds how many degrees Fahrenheit?
Answer: -22 degrees
●● Performance qualification of brazers shall remain in effect
indefinitely unless the brazer does NOT braze with the qualified
procedure for longer than what period of time? Answer: 6 months
●● Pipe labels shal be located at a maximum interval of how many feet?
Answer: 20
●● The installation of medical gas and vacuum systems shall be made
by experienced, qualified and competent installers. Installers shall be
certified to the requirements of which Code/Standard? Answer: ASSE
Standard 6010
●● Where medical gas systems operate at pressures other than the
standard gauge pressures, which of these is required to be listed on the
station outlet identification? Answer: name of the gas and operating
pressure
●● A gauge reading exceeding 200 psi. in a piping system is defined as
which type of pressure? Answer: High