EVALUATION 2026 QUESTIONS WITH
PRACTICE SOLUTION GRADED A+
◉ Track lighting with outlets in a bathroom is not allowed because ?
Answer: Track lighting has receptacle
◉ Where internal combustion engines are used as the prime motor,
an on site fuel supply shall be provided with an on premise fuel
supply sufficient for not less than ____ hours full demand operation
of the system Answer: 6 hours
◉ Fixed in place X-ray equipment properly supplied by a branch
circuit rated at not over ____ amperes shall be permitted to be
supplied through a suitable attachment plug cap and hard service
cable cord. Answer: 30 Amps
◉ Where skin effect exist the ferromagnetic envelope shall be
bonded at ____. Answer: Both ends
◉ GFCI protection at a carnival is not required for equipment at
circuit if the receptacle is of the ____type. Answer: Locking
,◉ The maximum voltage drop from service point to the last over-
current device in a dwelling unit? Answer: 4%
◉ Which of the following statements best describe the grounding
requirement for central vacuum outlet Answer: Accessible non
current carrying metal parts are required to be connected to an
equipment grounding conductor.
◉ In healthcare facilities, patient bed receptacles located in general
care areas shall be supplied by at least two branch circuits, which
____permitted to originate from two separate transfer switches on
the emergency system Answer: Are permitted
◉ Patient care areas of healthcare facilities ____ areas such as
business offices, corridors, lounges ,day rooms, or similar areas
Answer: Do not include
◉ The patient care area is any portion of the healthcare facility
where patients are intended to be ____or ____. Answer: Examined or
treated
◉ Each general care area patient bed location in a healthcare facility
must be provided with four ____ or ____ duplex receptacles Answer:
Single or two
,◉ A hospital is a building or portion thereof used for medical,
psychiatric,obstetrical , or surgical, care on a 24 hour basis of ____ or
more patients Answer: Four
◉ Where installed to reduce electrical noise for electronic
equipment, electrical continuity of the metal raceways shall not be
required and metal raceway can terminate a (an) ____ nonmetallic
fitting or spacer on electronic equipment Answer: Listed fitting
◉ Feeder and branch circuit conductors within ____ inches of a
Ballast shall have an insulation temperature rating not lower than
90°C (194°F) unless supplying a luminaiere marked as suitable for a
different insulation temperature Answer: 3 inches
◉ Manufactured wiring systems constructed with type MC cable
shall be supported and secured at intervals not exceeding ____ ft.
Answer: 6 ft
◉ Where a main bonding jumper or a system bonding jumper is a
screw only the screw shall be identified with a ____ that shall be
visible with the screw installed Answer: Green finish
◉ Plug fuses a 15 amperes and lower rating shall be identified by a
____ configuration of the window, cap, or other prominent part to
distinguish them from fuses of higher ampere rating Answer:
Hexagon
, ◉ The load for household electric clothes dryer's in a dwelling
unit(s) shall be either ____ watts (volt-amperes) or the nameplate
rating, which ever is larger, for each dryer served ? Answer: 5000
watts
◉ Service conductors installed as unjacketed multiconductor cable
shall have a minimum clearance of ____ windows that are designed to
be opened, doors, porches, stairs fire escape or similar locations.
Answer: 3 ft (36 inches)
◉ —— Cartridge fuses of the renewable type shall be permitted to
be used only for replacement in existing installation is where there
is no evidence of over-fusing or tampering. Answer: Class H
◉ Branch circuit conductors within ____inches of the ballast shall
have an insulation temperature rating not lower it 90°C 194°F
Answer: 3" inches
◉ The minimum radius of a field bend on trade size 1 "1/4 RMC is
____. Answer: 8
◉ In a dwelling unit which appliance is allowed to have a 24"inch
cord with Attachment ground plug ? Answer: Combination range
hood/microwave oven