QUESTIONS AND CORRECT ANSWERS
False - CORRECT ANSWER The use of adapters or conversation fittings adapt on gas
specific fitting to another shall be allowed for testing and verification only (T) or (F)
Medical/Instrument air sources - CORRECT ANSWER Which of the following
systems shall not be permited to be located in an outdoor enclosure?
Anesthetizing locations - CORRECT ANSWER Indoor locations for oxygen, nitrogen
oxide and mixtures of these gases shall not communicate with...
125 degrees 's - CORRECT ANSWER Cylinder in use and in storage shall be
prevented from reaching temperatures in excess of
Mechanical - CORRECT ANSWER Where the total volume of medical gases is greater
than 3,000 ft3, indoor supply locations shall be provided with what type of ventilation?
Pressure indicator - CORRECT ANSWER What is required downstream of each
regulator or immediately downstream of the isolating valves for the regulators?
Stainless steel - CORRECT ANSWER Relief valves for all positive pressure supply
systems shall have at least one relief valve made of brass, bronze or...
Check valve - CORRECT ANSWER I'm central supply systems, using gas cylinders, a
___ is at each connection for the cylinder or leads to prevent loss of gas in the event of
damage
Local, master - CORRECT ANSWER Manifolds for gas cylinders shall actuate a ___
signal and shall activate an indicator at the ___ alarm panels to indicate when or just before
changeover from one header to another
, Upstream - CORRECT ANSWER The gas produced by evaporation from the
secondary header in a cryogenic liquid cylinder system shall enter the supply system ___ of
the final line regulator
Emergency oxygen supply - CORRECT ANSWER Where the bulk cryogenic liquid
oxygen supply system is outside of and remote from the building served an ___ connection
shall be installed
Average days supply - CORRECT ANSWER In building emergency reserves shall
consist of at least an...
Human respiratory applications - CORRECT ANSWER Medical air sources shall be
used only for...
Manual shutoff valve - CORRECT ANSWER Medical air compressor systems shall
have a ___ to isolate each compressor for maintenance or repair
50% - CORRECT ANSWER Medical air compressor systems shall have a pressure
relief valve set at ___ above line pressure
Condensate trap - CORRECT ANSWER Aftercoolers where required shall be provided
with an individual..
All of the above.. relief valves, automatic and Manuel drains, and sight glasses - CORRECT
ANSWER Receivers for medical air shall be equipped with?
Final line regulator - CORRECT ANSWER Medical air filters shall be located
immediately upstream of the...
98% , 1 - CORRECT ANSWER Medical air filters shall be sized for 100% of the
systems peak calculated demand and be rated for a minimum of __ efficiency at __ micron or
greater