Maintenance/ LP Gas Master Qualifier: Laws, Rules &
Regulations Updated NEW EDITION 100% PASS
The point of transfer at a dispensing unit must be from Public ways, including public
streets, highways, thoroughfares, and sidewalks.
A. 10 feet
B. 15 feet
C. 25 feet - Ans A. 10 feet
Steel supports on vertical ASME containers shall be protected against fire exposure with a
material having a fire resistance rating of a least , except that continuous steel skirts that
have only one opening that is 18 in. or less in diameter shall have fire protection applied to the
of the skirts.
A. 3 hrs; outside
B. 2 hrs; outside
C. 3 hrs; inside - Ans B. 2 hrs; outside
Pressure relief devices installed in underground containers serving dispensing systems shall be
piped vertically upward to a point at least above the ground.
A. 2 feet
B. 6 feet
C. 10 feet - Ans C. 10 feet
, A remote emergency shut off device for either the internal valve or emergency shutoff valve is
required to be located not less than or more than from the liquid transfer point.
A. 10 ft ; 50ft
B. 10 ft; 100ft
C. 3 ft; 100ft - Ans C. 3 ft; 100ft
The markings for the switch or circuit breaker to shut off power in an emergency shall be visible
from .
A. The front entrance to the business
B. The Point of Transfer
C. An Orbital Space Station - Ans B. The Point of Transfer
Flexible connectors used in the installation of pumps so that pump casing is not subjected to
excessive strains transmitted to it by the suction and discharge piping shall not exceed in
overall length.
A. 60 inches
B. 36 inches
C. 24 inches - Ans B. 36 inches
Electrical Equipment install at vehicular fuel operations shall comply with the provisions of
and shall be approved for compliance with .
A. NFPA 58 6.25.2.2 - NFPA 58 6.25.2.3; NFPA 70- NFPA 58 Table 6.25.2.2
B. NFPA 58 Annex B; Rule 5J-20.045